background image

 

– 27 – 

RECOMMENDATIONS FOR PROPER PROTECTION 

The Following Recommendations for the Location of Fire and Burglary Detection Devices Help 
Provide Proper Coverage for the Protected Premises. 

 

Recommendations For Smoke And Heat Detectors 

With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the 
National Fire Protection Association's (NFPA) Standard #72 noted below.

 

Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the 
household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on 
each additional floor of a multi-floor family living unit, including basements. 

The installation of smoke detectors in kitchens, attics 

(finished or unfinished), or in garages is not normally recommended. 

 

For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining room, 
bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages. 

In addition, we recommend the following: 

•  Install a smoke detector inside every bedroom where a smoker sleeps. 
•  Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could 

be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed. 

 

DINING

KITCHEN

BEDROOM

BEDROOM

BEDROOM

BEDROOM

LIVING ROOM

BEDROOM

BDRM

DINING 

LIVING ROOM

TV ROOM

KITCHEN

BEDROOM

BEDROOM

TO
BR

LVNG RM

BASEMENT

KTCHN

.

CLOSED
DOOR

GARAGE

Smoke Detectors for Minimum Protection

Smoke Detectors for Additional Protection

Heat-Activated Detectors

BDRM

floor_plan-001-V1

 

•  Install a smoke detector inside bedrooms where 

electrical appliances (such as portable heaters, air 
conditioners or humidifiers) are used. 

•  Install a smoke detector at both ends of a hallway if 

the hallway is more than 40 feet (12 meters) long. 

•  Install smoke detectors in any room where an alarm 

control is located, or in any room where alarm 
control connections to an AC source or phone lines 
are made. If detectors are not so located, a fire 
within the room could prevent the control from 
reporting a fire or an intrusion. 

 

THIS CONTROL COMPLIES WITH NFPA 
REQUIREMENTS FOR TEMPORAL PULSE 
SOUNDING OF FIRE NOTIFICATION 
APPLIANCES. 

 

FCC/INDUSTRY CANADA

 

FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENTS 

The  user  shall  not  make  any  changes  or  modifications  to  the  equipment  unless  authorized  by  the  Installation  Instructions  or  User's  Manual.  
Unauthorized changes or modifications could void the user's authority to operate the equipment. 

CLASS B DIGITAL DEVICE STATEMENT 

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These 
limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can 
radiate  radio  frequency  energy  and,  if  not  installed  and  used  in  accordance  with  the  instructions,  may  cause  harmful  interference  to  radio 
communications.  However,  there  is  no  guarantee  that  interference  will  not  occur  in  a  particular  installation.  If  this  equipment  does  cause  harmful 
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the 
interference by one or more of the following measures: 

  Reorient or relocate the receiving antenna. 

  Increase the separation between the equipment and receiver. 

  Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. 

  Consult the dealer or an experienced radio/TV technician for help. 

INDUSTRY CANADA (IC) STATEMENTS 

This  device  complies  with  RSS210  of  Industry  Canada.  Operation  is  subject  to  the  following  two  conditions:  (1)  This  device  may  not  cause  harmful 
interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. 

This Class B digital apparatus complies with Canadian ICES-003. 

Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada. 

 

Summary of Contents for Entrepreneur 3000EN

Page 1: ...and System Installation Notes For full installation and programming information please refer to the Installation and Setup Guide K5305V8 or higher ARMED READY 1 2 3 4 5 6 7 8 9 0 STAY BYPASS CHIME IN...

Page 2: ...ories 25 Recommendations for Proper Protection 27 FCC Industry Canada 27 UL Notices 28 Uploading Downloading via the Internet 29 The Limitations of This Alarm System 30 Summary of Connections 31 Atten...

Page 3: ...mming Press 80 4229 or 4204 Relay modules powerline carrier devices or on board triggers Zone List Programming Press 81 Zone Lists for relay powerline carrier activation chime zones pager zones etc Al...

Page 4: ...be 00 for UL Commercial Burg installations 29 Enable IP GSM Communication Device Menu Mode pass through programming This is a Menu Mode command not a data field for programming IP GSM communication de...

Page 5: ...Open Close Test 3 Alarms Restore Cancel All 4 All except Open Close Test All 5 All All 50 BURGLARY DIAL DELAY 2 0 Delay Time Delay Disable values other than those stated will give unpredictable result...

Page 6: ...ORE RPT CODE 1 Any non zero entry enables report 71 TROUBLE RESTORE RPT CODE 10 Any non zero entry in first digit enables report 72 BYPASS RESTORE RPT CODE 00 Any non zero entry in first digit enables...

Page 7: ...use zone list 7 to enter those zones that require unlimited reporting these zones ignore the setting in entry 1 DOWNLOAD INFORMATION 94 95 94 DOWNLOAD PHONE No Enter up to 20 digits 0 9 11 for 12 for...

Page 8: ...able 1 enabled 181 50 60 HERTZ AC OPERATION 0 0 60 Hz 1 50 Hz CONFIGURABLE ZONE TYPE OPTIONS 183 181 182 CONFIGURABLE ZONE TYPE 90 IMPORTANT Be careful when selecting combinations of options for confi...

Page 9: ...e Refer to the communication device s installation instructions for details on enabling the Remote Services feature TOUCHPAD OPTIONS 190 196 NOTE Options for touchpad 1 address 16 are set by the facto...

Page 10: ...6 Short dial delay fault delay ENTRY 7 ENTRY 8 Display Faults Power Reset Verification Use Entry Delay 1 2 Use Exit Delay Respond as Interior Type 0 show alarms when armed disarmed 1 don t show alarm...

Page 11: ...1 57 1 BR 1 58 1 BR 1 59 1 BR 1 60 1 BR 1 61 1 BR 1 62 1 BR 1 63 1 BR 1 64 1 BR 1 95 09 N A N A N A touchpad 1 96 N A N A N A touchpad 3 99 07 N A N A N A touchpad NOTES Zone Type see chart on page 12...

Page 12: ...10 MAPPING Must program before using 80 OUTPUT TYPE OUTPUT TYPE Relay X10 Relay X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 1...

Page 13: ...or Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 24 Silent Burglary 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 25 24 Hr Non Alarm 02 Entry Exit 2 07 24 Hr Audible 14 C...

Page 14: ...07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Events Master Installer Installer Only 00 clear event 04 forced STAY arm 10 display custom words 8 10 01 device on off 05...

Page 15: ...has an emergency button Sends a report to the central station and provides an alarm sound at the touchpad and an audible external alarm Type 08 24 hour Auxiliary Alarm Assign to a zone containing an e...

Page 16: ...may not be used as fire or burglary zones in fire or UL burglar alarm installations The system can still be armed when these zone types are in a faulted condition Table of Device Addresses This Device...

Page 17: ...L 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKY...

Page 18: ...that the board rests on the correct row see Detail A b Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws see Detail B Notes Before in...

Page 19: ...resistance to damage from generally expected levels of lightning and electrical discharge and does not normally require an earth ground If an earth ground is desired for additional protection in area...

Page 20: ...For additional information regarding the 5800TM refer to the 5800TM s instructions Transmitters ULC Note for Canadian Units In accordance with ULC standards the RF supervision period for this control...

Page 21: ...ENROLL AS RF 5801 ENROLL AS UR OR RF 5800SS1 ENROLL AS RF LOOP 3 LOOP 1 LOOP 2 LOOP 4 YOU MUST ENROLL THIS BUTTON 5894PI ENROLL AS RF 5802 MN2 ENROLL AS UR OR RF LOOP 1 LOOP 1 LOOPS 1 3 LOOP 1 LOOP 1...

Page 22: ...keyswitch zone must be programmed to send opening and closing signals a UL commercial burglar alarm installation the keyswitch s tamper switch must be connected in to the alarm system This tamper swit...

Page 23: ...h aabout a twice per minute beeping at the touchpad indicates that a low battery condition exists in the wireless sensor displayed zone 00 indicates a wireless touchpad If the battery is not replaced...

Page 24: ...rn on and a LOW BATTERY report will be transmitted with a TEST report The touchpad will beep once about every 30 seconds as a reminder that the system is in the Test mode NOTE Wireless motion detector...

Page 25: ...es not confirm report transmissions 1 DIAL 0 WALK no special display on English Display Touchpads displays DISARMED READY TO ARM The following will be displayed accompanied by 2 beeps if test is succe...

Page 26: ...ers 6150RFADT 6160RF 6270ADT Touch Screen Touchpad iCenter Advanced User Interface RF Receivers 5881L 5882L accepts up to 8 transmitters 5881M 5882M accepts up to 16 transmitters 5881H 5882H accepts u...

Page 27: ...in any room where an alarm control is located or in any room where alarm control connections to an AC source or phone lines are made If detectors are not so located a fire within the room could preven...

Page 28: ...radation du service dans certaines situations Les r parations de mat riel nomologu doivent tre coordonn es par un repr sentant d sign par le fournisseur L entreprise de t l communications peut demande...

Page 29: ...nt 7845GSMADT System Requirements Internet Communication At the Installation Site Appropriate Internet Communication Module 7720P Programmer Broadband Internet Access for wired modules Broadband Cable...

Page 30: ...s closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detec...

Page 31: ...MINALS SEE INSTRUCTIONS REMOTE TOUCHPADS EACH PARTITION CAN USE 6150ADT OR 6160ADT TOUCHPADS SEE INSTRUCTIONS PROVIDED WITH TOUCHPAD LOCAL PROGRAMMING MUST BE DONE WITH A 6160ADT BUT NEED NOT REMAIN I...

Page 32: ...ORMATION For the latest warranty information please go to www honeywell com security hsc resources wa ADT Security Services Inc One Town Center Rd Boca Raton FL 33486 Copyright 2003 K9287V6 K9287V6 8...

Reviews: