ADC AD120i Installation & Operator'S Manual Download Page 22

22

American Dryer Corp.

113546 - 2

!

Regulated Gas Valve

Refer to “Gas Pressure Adjustment” (this page) to adjust
the gas valve to the appropriate burner pressure listed
on 

page 19

.  The supply pressure must also match what

is listed on 

page 19

 for the type of gas to be used.

IMPORTANT:

 Conversion must be performed by competent

technicians in accordance with local and state codes.
IMPROPER ASSEMBLY OR ADJUSTMENTS CAN CAUSE
HAZARDOUS CONDITIONS.

Gas Pressure Adjustment

IMPORTANT:

 When converting from one gas to another

with regulated gas conversion kit, the following procedures
must be performed.

Disconnect electrical power to the dryer.
To adjust gas valve’s internal regulator, remove the regulator
vent cap (figure 5).  Turn the plastic adjustment screw in the
valve.  Turn the screw clockwise to raise pressure and
counterclockwise to lower pressure.
Gas (burner) pressures are measured with the burner in
operation for all burner adjustment conditions.  Refer to “Gas
Pressure Test Procedure” for instructions on this procedure.
Therefore once the necessary adjustments have been made,
the dryer must be operated in a heating cycle to verify that the
pressure is correct.  If it is not correct, you must discontinue
the power to the unit and make further adjustments.  Repeat
these steps as many times as necessary to achieve the correct
burner pressure.  Once the adjustment of the valve is
complete, the vent cap must be replaced and sealed with, for
example, paint to prevent maladjustment by the user.  Operate
the dryer through one complete cycle to ensure proper
operation.

Warning (CE Dryers)

This appliance must only be operated with the gas
type indicated on the dryer’s rating plate.  If the

appliance is converted (gas type changed), a new rating
plate must be obtained from American Dryer Corporation
(dryer’s serial number is required to purchase a conversion
kit).

Gas Pressure Testing

For proper operation, the gas pressure must be correct,
consistent and maintained at the gas pressure rates shown
on 

page 19

.  Provisions are made at the gas valve for taking

gas pressure readings.
There are two types of devices used to measure gas pressure.
They are the spring/mechanical type gauge and the
manometer.  The use of the spring/mechanical type gauge is
not recommended because they are very easily damaged and
are not always accurate.  The preferred type of gauge is the
manometer because it is a simple device to use and is highly
accurate.  A manometer is simply a glass or transparent plastic
tube with a scale graduated in inches or millibars.  When it is
filled with water and pressure is applied, the water in the tube
rises, showing the exact gas pressure.

Gas Pressure Test Procedure

Turn gas cock in gas supply line to “OFF” position.
CE Dryers: Back out miniature screw inside pressure tap and
attach manometer.  Refer to figure 5 on 

page 21

.

Non-CE Dryers: Install pressure tap and attach manometer.
Refer to figure 5 on 

page 21

.

Turn gas cock to “ON” position.
Start the dryer in Heat Mode and wait for ignition.  Gas manifold
pressure should be as shown on 

page 19

.

If the gas pressure needs to be adjusted, refer to “Gas
Pressure Adjustment” (this page).
Once test is complete, turn gas cock to “OFF” position.
Remove manometer.  Tighten screw inside the pressure tap
(50 Hz dryers) or reinstall plug (60 Hz dryers).
Turn gas cock to “ON” position and check for leaks with soap
solution with main burner “ON.”

Water Information_____________________

(For Optional Fire Suppression System)
Before You Start
Check Local Codes and Permits

Call your local water company or the proper municipal authority
for information regarding local codes.

IMPORTANT:

 It is your responsibility to have all plumbing

connections made by a qualified professional to ensure that
the plumbing installation is adequate and conforms to local,
state, and federal regulations or codes.
It is the installer’s or owner’s responsibility to see that the
required water pressure, pipe size, or connections are
provided.  The manufacturer assumes no responsibility if
the fire suppression system is not connected, installed, or
maintained properly.

Installation
Water Supply

The fire suppression system must be supplied with a minimum
water pipe size of 1/2-inch (12.7 mm) and be provided with 40
psi +/- 20 psi (2.75 bar +/- 1.37 bar) of pressure.
If the rear area of the dryer or the water supply is located in
an area where it will be exposed to cold/freezing temperatures,
provisions must be made to protect these water lines from
freezing.

Warning

If the water in the supply line or water solenoid
valve freezes, the fire suppression system will be

inoperative!!

Water Connections

The water connection is made to a 3/4”-11.5 NH hose or 3/4”
B.S.P. adaptor, depending on the destination country.  A flexible
supply line/coupling must be used in an effort to avoid
damaging the electric water solenoid valve.

NOTE: 

The 3/4”-11.5 NH is a standard hose coupling screw

thread.  It is not to be confused with 3/4” N.P.T., or 3/4
B.S.P.   The sealing of an NH connection is made with a
washer as opposed to the mating threads of an N.P.T. or
B.S.P. assembly.  The 3 thread designs are not compatible.

!

Summary of Contents for AD120i

Page 1: ...isin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incendies L installation et l entretien doivent tre assur s par un installateur ou...

Page 2: ...ur order is processed accurately and promptly These instructions are only valid if the following country code is on the appliance If this code is not present on the appliance it is necessary to refer...

Page 3: ...he following installation instructions apply Installations and repairs must be performed by a qualified or licensed contractor plumber or gasfitter qualified or licensed by the State of Massachusetts...

Page 4: ...terials Drying in a heated tumbler may damage plastics or rubber and also may be a fire hazard The possible presence of residual quantities of aggressive or decomposed chemicals in the load may produc...

Page 5: ..._ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ _________...

Page 6: ...IRBORNE SOUND LEVEL 69 dB A DRYERS PER 20 40 CONTAINER 4 9 DRYERS PER 48 53 TRUCK 10 12 VOLTAGE AVAILABLE 208 480V 1 3 2 3 4w 50 60 Hz APPROXIMATE NET WEIGHT 1 440 lb 653 17 kg APPROXIMATE SHIPPING WE...

Page 7: ...claundry com 7 NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation Specifications ______________________________________________________...

Page 8: ...tible construction as noted in this manual refer to Dryer Enclosure Requirements section Provisions must be made for adequate clearances for servicing and for operation as noted in this manual refer t...

Page 9: ...onsole Module 1 Remove the outer top top back guard bottom back guard and rear electrical box cover refer to the Component Identification drawing 2 Remove 8 bolts washers and lock washers L figure 1 t...

Page 10: ...o its mating plug This plug is similar to the one in the lower right corner that was disconnected earlier 9 Reinstall the retaining screws top and bottom 10 Reinstall the bottom hinge block This was t...

Page 11: ...e exhaust ductwork system Exhaust back pressure measured by a manometer magnehelic in the exhaust duct must be no less than 0 and must not exceed 0 7 in WC 1 7 mb Fresh Air Supply Requirements _______...

Page 12: ...e nearest obstruction refer to the diagram Exhaust Transition Piece This dryer is equipped with a 12 inch to 10 inch exhaust transition piece installed for use with 10 inch ducting If the exhaust duct...

Page 13: ...proper venting information Multiple Dryer Common Venting If it is not feasible to provide separate exhaust ducts for each dryer ducts from individual dryers may be channeled into a common main duct T...

Page 14: ...14 American Dryer Corp 113546 2 MULTIPLE DRYER VENTING HORIZONTAL AT COMMON DUCT MULTIPLE DRYER VENTING VERTICAL AT COMMON DUCT...

Page 15: ...wire size 4 24 14 Not available until September 2014 Grounding A ground earth connection must be provided and installed in accordance with local state and national regulations or codes of the country...

Page 16: ...be grounded A ground lug has been provided for this purpose Input connection wiring must be sized properly to handle the dryer s current draw This information is printed on the dryer s rating plate I...

Page 17: ...re the input wiring enters 3 Phase 3 Wiring Connections Hookup The electrical connections on all 3 phase 3 gas and steam dryers are made into the rear service box located at the upper left area of the...

Page 18: ...atings shown on the rating plate are for elevations up to 2 000 feet 610 meters unless elevation requirements of over 2 000 feet 610 meters were specified at the time the dryer order was placed with t...

Page 19: ...Input Gas Consumption Orifice Injector Data For CE European Models Only GAS SPECIFICATIONS FOR NON CE APPROVED DRYERS Gas Type Nominal Heating Value Supply Pressure Gross Heat Input Orifice Size Orif...

Page 20: ...ccessible for a pressure gauge connection must be installed in the main gas supply line immediately upstream of the dryers IMPORTANT Pipe joint compounds that resist the action of natural L P and buta...

Page 21: ...tructions included in kit envelope 92 1022 supplied 9 To convert the gas valve for use with regulated L P gas refer to the instructions included in kit envelope 92 0659 supplied 10 Reverse procedure f...

Page 22: ...ly a glass or transparent plastic tube with a scale graduated in inches or millibars When it is filled with water and pressure is applied the water in the tube rises showing the exact gas pressure Gas...

Page 23: ...ly in place Be sure the lint door drawer is securely in place Rotate the tumbler drum by hand to be sure it moves freely Check bolts nuts screws terminals and fittings for tightness and security Check...

Page 24: ...mation ___________ Service Service must be performed by a qualified trained technician If service is required contact the reseller from whom the equipment was purchased If the reseller cannot be conta...

Page 25: ...t be accepted IMPORTANT No replacements credits or refunds will be issued if the claim cannot be processed due to insufficient information The party filing the claim will be notified in writing either...

Page 26: ...exhaust and ventilation gases reducing dryer performance Cleaning of the dryer s internal exhaust may require removing the lint screen See the instructions above for removing the lint screen Check an...

Page 27: ...____ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______...

Page 28: ...IL SWITCH CLOSED FAULT Sail switch is closed should be open at the start of a cycle O O O SAIL SWITCH OPEN FAULT Sail switch remained open after the cycle started Should have closed BURNER HIGH LIMIT...

Page 29: ...closed before starting SAIL SWITCH OPEN Sail switch failed to close after starting BURNER HI LIMIT Oven thermostat switch has opened EXHAUST HI LIMIT Tumbler thermostat switch has opened BURNER CONTRO...

Page 30: ...ADC Part No 113546 2 08 13 14...

Reviews: