EURODIM TWIN TECH
User Manual - page 37
Issue 2.1
www.adbstagelight.com
7.6 Local / Remote Controller selector switch CPU1 – CPU2 – Automatic
The jumper J1 is by default NOT mounted.
-
Power supply voltage: Vcc = 24V (thru 1.5K and protection fuses on PCB3031)
-
Enable_CPU signals are active high
-
(*)
0 = terminal connected to 0 V; 1 = terminal is open
-
(**)
Manual selection by the user
-
(***)
Only for information
-
(****)
Value forced by presence of Jumpers J1
For remote CPU or controller selection, use a shielded cable of 3 x 0.5 mm
²
. The shield
should at one end be connected to PE. See wiring and interconnection diagram in 30-490
and 30-500.
The Controller or CPU selector switch is
located next to the CPU slots. The
connection for the remote selector switch is
provided in the right compartment on the
PCB 3031. Please see the attached drawing
for the exact wiring of the switch.
The following table explains the use of the
local and remote switch.
Summary of Contents for EURODIM Twin Tech
Page 1: ...M 3213 1106 01 213 Installation Manual V 1 2 EURODIM Twin Tech ...
Page 2: ......
Page 13: ...EURODIM TWIN TECH User Manual page 11 Issue 2 1 www adbstagelight com 3 DESCRIPTION ...
Page 50: ...EURODIM TWIN TECH User Manual page 48 Issue 2 1 www adbstagelight com 3 8 8 142 990 596 216 ...
Page 63: ...EURODIM TWIN TECH User Manual page 61 Issue 2 1 www adbstagelight com 14 CONFIGURATION TABLES ...
Page 65: ...EURODIM TWIN TECH User Manual page 63 Issue 2 1 www adbstagelight com ...
Page 67: ...EURODIM TWIN TECH User Manual page 65 Issue 2 1 www adbstagelight com Notes ...
Page 68: ......
Page 70: ......
Page 71: ...M 3213 E 09p Subject to modifications www adbstagelight com info adblighting com ...