5.1 Controller Electronics - CPU/ PSU crate
The CPU/ PSU crate is already mounted in our factory. If a removal is required, loosen the
4 screws and remove the complete crate gently. Replace the connected flat cables with
caution.
5.2 Supply voltage
The high voltage/low voltage power transformer MUST ABSOLUTELY provide a three
phase star system with available neutral (3NPE-400), and rated line voltage 380 V to 415
V between phases and 220 V to 240 V rated voltage between each phase and neutral.
See “Protections” for more details.
The supply cable must have the four current-carrying power conductors (not necessarily
the PE conductor) twisted under the same sleeve, in order to reduce the electrical noise
induced by large dimmed currents.
The neutral conductor must be of equal or larger size than the phase conductors.
See the Appendix to this manual for more details about power supply systems for dimmer
systems.
Summary of Contents for EURODIM Twin Tech
Page 1: ...M 3213 1106 01 213 Installation Manual V 1 2 EURODIM Twin Tech ...
Page 2: ......
Page 13: ...EURODIM TWIN TECH User Manual page 11 Issue 2 1 www adbstagelight com 3 DESCRIPTION ...
Page 50: ...EURODIM TWIN TECH User Manual page 48 Issue 2 1 www adbstagelight com 3 8 8 142 990 596 216 ...
Page 63: ...EURODIM TWIN TECH User Manual page 61 Issue 2 1 www adbstagelight com 14 CONFIGURATION TABLES ...
Page 65: ...EURODIM TWIN TECH User Manual page 63 Issue 2 1 www adbstagelight com ...
Page 67: ...EURODIM TWIN TECH User Manual page 65 Issue 2 1 www adbstagelight com Notes ...
Page 68: ......
Page 70: ......
Page 71: ...M 3213 E 09p Subject to modifications www adbstagelight com info adblighting com ...