12.1.4.4. Slope 1 Settings
The adjustment of the slope for the relationship between the PWM input and
the 0-10V DC output can be adjusted as shown in the graph below.
Pump connector
AGU2.551 X2
GND
Pin 1, M
0-10V control
Pin 2, UX41
12.1.5. UIN 235783 LPB Interface
Refer to the Boiler installation manual as required when carrying out the
installation.
This option kit enables communication over the LPB (Local Process Bus)
between a boiler and another external LPB device, boiler or External module.
Note:
For operation in a cascade, each boiler in the cascade requires an LPB
interface fitting. One of the boilers must designated as a Cascade master.
12.1.5.1. Location
The location is fixed and is shown below:
(insert photograph)
For cascade operation a 2-core cable is required to be run between the Boiler
LPB terminals and the associated Boiler LPB terminals, for LPB accessories
between the Boiler LPB terminals and the External module LPB terminals.
Note:
In an electrically noisy environment, it is recommended that a screened
cable be used. The screen should only be connected to ground at one end.
Summary of Contents for EVO S 100
Page 2: ......
Page 13: ... EVO S Installation Commisioning and Servicing Instructions 13 EN ...
Page 44: ...EVO S Installation Commisioning and Servicing Instructions EN 44 Figure 19 Wiring diagram ...
Page 45: ...EVO S Installation Commisioning and Servicing Instructions 45 EN ...
Page 149: ...EVO S Installation Commisioning and Servicing Instructions 149 EN ...
Page 150: ...EVO S Installation Commisioning and Servicing Instructions EN 150 ...
Page 151: ...EVO S Installation Commisioning and Servicing Instructions 151 EN ...
Page 152: ...EVO S Installation Commisioning and Servicing Instructions EN 152 ...
Page 153: ...EVO S Installation Commisioning and Servicing Instructions 153 EN ...