EVO S
, Installation, Commisioning and Servicing Instructions
105
EN
BOILER PUMP NOT FROM ACV
page 3 / 3
Use the following settings to determine the values of the previous section's parameters by
respecting the data presented in the summary table of the flow rates below:
Model (kW)
40
60
70
80
100
120
150
Min. flow (l/min)
9.5
19.2
19.2
38.3
38.3
50.0
57.3
2322 (%) with our circulator kits
34
42
35
40
40
45
42
Max. flow (l/min)
28.7
39.3
50.0
69.3
71.7
86.0
103.8
2323 (%) with our circulator kits
74
78
78
75
77
74
79
Follow steps 1 and 2 to find the minimum flow command and repeat these same steps to set the
maximum flow command.
Step 1
Line No. Value
• Menu
Input/output tests
Define the control value in % to control the boiler pump speed. The 0-100% scale roughly
corresponds to the 0-10V control scale.
Request via manual control
Test output P1 (7713)
---% (0 to 100%)
For example, if the pump from the kit is used for a 70kw boiler, the value to be entered here
would be 35%.
Step 2
Line No. Value
• Generator diagnostics
menu
Check that the water flow in the boiler is as expected
Reading the boiler water flow
Boiler flow (8366)
--- (l/min)
For example, for a 70 kW boiler, the value to be shown here is 19.2 l/min (+/-0.2 l/min).
If the flow rate for your model does not match what is shown in the above table, please reset a
speed control beginning from step 1.
Summary of Contents for EVO S 100
Page 2: ......
Page 13: ... EVO S Installation Commisioning and Servicing Instructions 13 EN ...
Page 44: ...EVO S Installation Commisioning and Servicing Instructions EN 44 Figure 19 Wiring diagram ...
Page 45: ...EVO S Installation Commisioning and Servicing Instructions 45 EN ...
Page 149: ...EVO S Installation Commisioning and Servicing Instructions 149 EN ...
Page 150: ...EVO S Installation Commisioning and Servicing Instructions EN 150 ...
Page 151: ...EVO S Installation Commisioning and Servicing Instructions 151 EN ...
Page 152: ...EVO S Installation Commisioning and Servicing Instructions EN 152 ...
Page 153: ...EVO S Installation Commisioning and Servicing Instructions 153 EN ...