D. OPERATING DESCRIPTION
The heating water law is programmed on the NAVISTEM B3100, with or without a low temperature limit
and with a weekly programme.
The AGU2.550 interfaces are used to control the two three-way regulating valves of the heating
networks. The other 2 will be controlled by the RVS63 integrated in an external unit.
The boiler operates in variable flow temperature according to the outdoor temperature measured by
the exterior sensor QAC 34, without a low temperature limit.
The production of domestic hot water is controlled by the NAVISTEM B3100 using the QAZ 35 sensor
in the tank.
Diagram: EVO S-4
page 2 / 8