Installation and Commissioning Guide - Package Commercial Unit
Doc. Part No. 0525-055 Ver. 9 220308
Installation and Commissioning Guide
Package Commercial Unit
32
17.05. PCG260U/V
FAN PERFORMANCE DATA
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
1120
55
440
60
542
64
634
69
731
82
832
99
934
1150
57
468
62
574
67
677
72
769
86
872
1200
61
521
66
624
71
728
77
835
93
943
1250
66
587
71
692
76
797
84
909
1300
71
654
76
765
81
874
93
995
1320
73
682
78
786
83
904
MOTOR / BLOWER LIMIT
1350
76
723
80
818
86
950
1400
81
795
86
912
93
1036
1450
86
862
92
1002
NOTES:
Performance Fan Curve shown is at Dry Coil Condition. Airflow
should be reduce with respect to the moisture content in the
air. All data provided does not include filters. Please review filter
manufacturer for application. 2.5 m/s face velocity point will
occur at 1406 l/s.
NOTES:
W
= Indoor Fan Power, Watts
PWM
= Pulse Width Modulation Setting, % PWM
(Adjustable through CPI3-2 Board located in electrical panel).
Factory PWM Setting = 78 % PWM for 100 Pa.
- Data in the box indicates Factory Default Setting.
JUMPER PIN
POSITION
INDOOR FAN
A
SCG400E
PCG400U/V/L/R
B
PCG340U/V/L/R
C
PCG330U/V/L/R
D
PCG300L/R
PKA300L/R
E
SCG290E
PCG290U/V/L/R
F
SRG260E
PCG260U/V
(CPI3-1) COMMERCIAL PWM INTERFACE BOARD
NOTES:
LED will show PWM without %.
Example: 78% PWM = 78 in LED.
LED adjustments are in 1 digit increments.
JUMPER PIN
SET AS PER
TABLE BELOW
PWM
ADJUSTMENT
(POTENTIOMETER)
CPI 3
23787-3
C3
DISP2 DISP1
MODEL
A
B
C
D
E
F
ADJUST
V2
C2
P3
C1
+
+
P1
P2
V1.0
U4
U3
R11
R12
R13
R14
R15
C5
D3
R3
R4
C7
R2
R1
RV1
TRA-0100-R
D1
D2
P5
TX1
240VAC OUT
INPUT
R10
C8
P6
GND
0 - 10
V
PWM1 OUT
PWM2 OUT
P4
DAMAGE DUE TO
INCORRECT WIRING
VOIDS WARRANTY
CPI3-
1
S/No:
11G1
2276
IF
ON/OFF
IF
PWR
240VAC IN
ActronAir
LED FAN
PWM
DISPLAY
Nominal Airflow = 1320 l/s
AIRFLOW (l/s)
APPLICATION RANGE
EXTERNAL S
TA
TIC PRE
SSURE (P
a)
0
50
100
150
200
250
300
1100
1150
1200
1250
1300
1350
1400
1450
1100
1150
1200
1250
1300
1350
1400
1450
0
50
150
200
250
300
100
1320
78% PWM
55% PWM
60% PWM
65% PWM
70% PWM
75% PWM
80% PWM
85% PWM
90% PWM
95% PWM
99% PWM
MOTOR / BLOWER LIMIT