17.02. PCG173U/V
FAN PERFORMANCE DATA
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
75
100
125
150
175
200
225
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
770
66
288
70
333
74
371
79
422
84
474
88
512
93
561
98
610
775
67
294
71
335
75
374
80
428
85
476
89
518
94
571
99
618
800
71
315
75
358
80
404
85
457
89
502
93
550
99
610
825
74
340
79
383
84
436
88
482
93
535
97
584
850
78
364
83
413
88
463
92
513
97
568
875
82
390
87
445
92
494
96
549
MOTOR / BLOWER LIMIT
900
87
431
92
483
97
547
NOTES:
Performance Fan Curve shown is at Dry Coil Condition. Airflow
should be reduce with respect to the moisture content in the
air. All data provided does not include filters. Please review filter
manufacturer for application. 2.5 m/s face velocity point will
occur at 1028
l/s.
NOTES:
W
= Indoor Fan Power, Watts
PWM
= Pulse Width Modulation Setting, % PWM
(Adjustable through CPI3-2 Board located in electrical panel).
Factory PWM Setting = 88 % PWM for 100 Pa.
- Data in the box indicates Factory Default Setting.
JUMPER PIN
POSITION
INDOOR FAN
A
NOT USED
B
NOT USED
C
PCG153U/V
D
PCG173U/V
E
PCG203U/V
F
PCG233U/V
(CPI3-2) RESIDENTIAL PWM INTERFACE BOARD
NOTES:
LED will show PWM without %.
Example: 88% PWM = 88 in LED.
LED adjustments are in 1 digit increments.
CPI 3
23787-3
C3
DISP2 DISP1
MODEL
A
B
C
D
E
F
ADJUST
V2
C2
P3
C1
+
+
P1
V2.1
U4
U3
R11
R12
R13
R14
R15
C5
D3
R3
R4
C7
R2
R1
RV1
TRA-0100-R
D1
D2
P5
INPUT
R10
C8
P6
GND
0 - 10
V
PWM1 OUT
DAMAGE DUE TO
INCORRECT WIRING
VOIDS WARRANTY
CPI3-2
S/N: XXXXXXXX
IF
ON/OFF
IF
PWR
240VAC IN
ActronAir
LED FAN
PWM
DISPLAY
JUMPER PIN
SET AS PER
TABLE BELOW
PWM
ADJUSTMENT
(POTENTIOMETER)
FAN CURVE
0
25
50
75
100
125
150
175
200
225
250
275
700
725
750
775
800
825
850
875
900
AIRFLOW (l/s)
Nominal Airflow = 850 l/s
275
250
225
200
175
150
125
100
75
50
25
0
EXTERNAL S
TA
TIC PRE
SSURE (P
a)
700
725
750
775
800
825
850
875
900
APPLICATION RANGE
99% PWM
95% PWM
90% PWM
85% PWM
80% PWM
70% PWM
65% PWM
60% PWM
88% PWM
75% PWM
MOTOR / BLOWER LIMIT