background image

SERIES IP440 INDUSTRIAL I/O PACK                                32-CHANNEL ISOLATED DIGITAL INPUT MODULE
___________________________________________________________________________________________

- 15 -

INPUTS

Input Channel Configuration.......32 Optically isolated bipolar

inputs.  For DC or AC voltage
applications  within specified
range limits.

Isolation Medium........................Photo-transistor optocoupler,

Siemans SFH628A-4 or
equivalent.  UL & VDE rated for
isolation voltages up 400V DC or
AC rms (optocoupler only).

Bipolar Input Voltage Range.......AC or DC Volts peak, per model

number: 

±

4V to 

±

18V (Model

IP440-1); 

±

 16V to 

±

 40V (Model

IP440-2); 

±

 38V to 

±

 60V (Model

IP440-3).  Range is determined
by value of the input current
limiting SIP resistors installed on
the module (R5, R6, R7, R8).

Input Threshold..........................Refer to Table below.  The

IP440-1 model may be used to
interface with open-drain TTL
outputs when used with an
appropriate pullup to +5V (see
Drawing 4501-603).

IP440

INPUT RANGE

ON Threshold Voltage

Range

(AC or DC Peak)

MIN

TYP

MAX

-1

± 4V to ±18V

±1V

±2V

±4V

-2

±16V to ±40V

±4V

±6.4V

±16V

-3

±38V to ±60V

±8V

±12.9V

±38V

Input Hysteresis.........................80mV Typical.
Input Capacitance......................45pF Typical.
Turn-On Time............................Measured to point of positive

event interrupt detection
(IntReq0 pulled low) - 15us
Typical (25

°

C) for a 0 to

threshold input step. Time
decreases as magnitude of the
step is increased above
threshold.

Turn-Off Time.............................Measured to the point of

negative event interrupt detection
(IntReq0 pulled low) - 35us
Typical (25

°

C) for a threshold to

0V input step.  Time increases
as magnitude of the step value is
increased from the threshold.

Input Debounce..........................Each input includes debounce

circuitry with variable debounce
times.  Debounce times are
programmable and derived from
the 8MHz system clock, in
combination with the debounce
duration register value.
Debounce times are applied at
the ASIC input and do not
include optocoupler delay time.
Debounce values of 3-4us, 48-
64us, 0.75-1ms, and 6-8ms may
be configured.  Note that the
debounce clock must be enabled
via the Debounce Select register
to utilize debounce.

Interrupts....................................32 channels of interrupts may be

configured for high-to-low, low-to-
high, and change-of-state (two
inputs required) event types.

Forward Voltage Drop................1.1V Typical, 1.5V Maximum

(Diode) + I*R.  Series input
current-limiting resistors are 2.2K
(IP440-1), 12K (IP440-2), or 27K
(IP440-3) and installed on board.

Input Current..............................Varies per model number and

input signal voltage level.  For
Model IP440-1, the current is
computed by dividing the signal
level minus 1.5V, by its current
limiting resistor (2200

 for

IP440-1, 12000

 for IP440-2,

and 27000

 for IP440-3).

INDUSTRIAL I/O PACK COMPLIANCE

Specification..............................This module meets or exceeds

all written Industrial I/O Pack
specifications per revision 0.7.1.

Electrical/Mechanical Interface..Single-Size IP Module.

IP Data Transfer Cycle Types Supported:

Input/Output (IOSel*)............D16 or D08 least significant byte

read/write of port data.

ID Read (IDSel*)...................32 x 8 ID PROM read on

D0..D7.

Interrupt Select (INTSel*).....8-bit word (D08) read of Interrupt

Vector Register contents.

Access Times (8MHz Clock):

All Read/Write Cycles..........0 wait states (250ns cycle).

APPENDIX

CABLE:  MODEL 5025-550-x (Non-Shielded)
               MODEL 5025-551-x (Shielded)

Type:  Flat Ribbon Cable, 50-wires (female connectors at both

ends).  The ‘-x’ suffix designates the length in feet (12 feet
maximum).  Choose shielded or unshielded cable according
to model number.  The unshielded cable is recommended for
digital I/O, while the shielded cable is recommended for
optimum performance with precision analog I/O applications.

Application:  Used to connect a Model 5025-552 termination

panel to the AVME9630/9660 non-intelligent carrier board A-
D connectors (both have 50-pin connectors).

Length:  Last field of part number designates length in feet (user-

specified, 12 feet maximum).  It is recommended that this
length be kept to a minimum to reduce noise and power loss.

Cable:  50-wire flat ribbon cable, 28 gage.  Non-Shielded cable

model uses Acromag Part 2002-211 (3M Type C3365/50 or
equivalent).  Shielded cable model uses Acromag Part 2002-
261 (3M Type 3476/50 or equivalent).

Headers (Both Ends):  50-pin female header with strain relief.

Header - 

Acromag Part 1004-512 (3M Type 3425-6600 or

equivalent).  

Strain Relief -

 Acromag Part 1004-534 (3M Type

3448-3050 or equivalent).

Keying:  Headers at both ends have polarizing key to prevent

improper installation.

Schematic and Physical Attributes:  For Non-Shielded cable

model, see Drawing 4501-462.  For Shielded cable model,
see Drawing 4501-463.

Shipping Weight:  1.0 pound (0.5Kg) packaged.

Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com

Summary of Contents for IP440 Series

Page 1: ...ess underutilized and idle equipment along with credit for buybacks and trade ins Custom engineering so your equipment works exactly as you specify Critical and expedited services Leasing Rentals Demo...

Page 2: ...RATED 30765 South Wixom Road P O BOX 437 Wixom MI 48393 7037 U S A Tel 248 624 1541 Fax 248 624 9234 Copyright 1996 Acromag Inc Printed in the USA Data and specifications are subject to change without...

Page 3: ...his is especially important where economic property loss or human life is involved It is important that the user employ satisfactory overall system design It is agreed between the Buyer and Acromag th...

Page 4: ...your carrier board to ensure compatibility with the following interface products Cables Model 5025 551 X Shielded Cable or Model 5025 550 X Non Shielded Cable A Flat 50 pin cable with female connector...

Page 5: ...in the mating area Threaded metric M2 screws and spacers are supplied with the module to provide additional stability for harsh environments see Mechanical Assembly Drawing 4501 434 The field and logi...

Page 6: ...d to avoid incorrect assembly 3 0 PROGRAMMING INFORMATION ADDRESS MAPS This board is addressable in the Industrial Pack I O space to control the configuration and status monitoring of 32 digital input...

Page 7: ...IN24 IN31 07 08 Not Driven4 READ WRITE2 Port 4 NOT USED 09 0A Not Driven4 READ WRITE2 Port 5 NOT USED 0B 0C Not Driven4 READ WRITE2 Port 6 NOT USED 0D 0E Not Driven4 READ WRITE Port 7 WRITE MASK REGI...

Page 8: ...0 ODD Base Addr INDEPENDENT FIXED FUNCTION REGISTERS 10 1C NOT USED2 11 1D 1E Not Driven1 READ WRITE Interrupt Enable Register Bit 0 1 enables INTREQ0 Software Reset Generator Bit 1 1 Generates Reset...

Page 9: ...of this model Writing a 1 to bits 0 3 of the Mask Register will mask ports 0 3 respectively from inadvertent writes A read of this register will return the status of the mask in bits 0 3 Enhanced Mode...

Page 10: ...IN31 Bank Select Register Enhanced Mode Bank 1 Port 7 Write Only Bits 6 7 of this register are used to select monitor the bank of registers to be addressed In Enhanced Mode three banks banks 0 2 of e...

Page 11: ...t Cycles INTSEL to occur This bit is cleared following a system reset but not a software reset see below Writing a 1 to the bit 1 position of this register will cause a software reset to occur be sure...

Page 12: ...440 2 models and 38 60V IP440 3 models Inputs are non inverting and inputs left floating not recommended will register a low false 0 input indication In both the Standard and Enhanced operating modes...

Page 13: ...ting the interrupt have been cleared or return to normal and the event sense flip flop has been cleared by writing 0 to the corresponding bit position of the Event Sense Status Register or until the I...

Page 14: ...ity of data contention between the built in output circuitry and the devices driving these inputs Write 01H to the port 7 address to mask writes to port 0 11 Read 01H from the port 7 address to verify...

Page 15: ...cedures in Section 2 Preparation For Use have been followed Also refer to the documentation of your carrier board to verify that it is correctly configured Replacement of the module with one that is k...

Page 16: ...aximum Diode I R Series input current limiting resistors are 2 2K IP440 1 12K IP440 2 or 27K IP440 3 and installed on board Input Current Varies per model number and input signal voltage level For Mod...

Page 17: ...ensity ribbon cable connectors coming from the APC8600 carrier board Acromag cable Model 5029 900 to screw terminals for direct wired interfaces This panel facilitates the connection of up to 50 field...

Page 18: ...Artisan Scientific Quality Instrumentation Guaranteed 888 88 SOURCE www artisan scientific com...

Page 19: ...Artisan Scientific Quality Instrumentation Guaranteed 888 88 SOURCE www artisan scientific com...

Page 20: ...Artisan Scientific Quality Instrumentation Guaranteed 888 88 SOURCE www artisan scientific com...

Page 21: ...Artisan Scientific Quality Instrumentation Guaranteed 888 88 SOURCE www artisan scientific com...

Page 22: ...uipment Have surplus equipment taking up shelf space We ll give it a new home Learn more Visit us at artisantg com for more info on price quotes drivers technical specifications manuals and documentat...

Reviews: