Alliance Intelligent Battery Series
TM
User’s Guide
© 2020 American Battery Solutions Inc. All rights reserved. The data herein is intended as a guide and does not reflect the specification range for any particular property of this
product. Such data is based upon analysis of representative samples and not the actual product shipped. We based the information on data believed to be reliable on the date
compiled, but we do not represent, warrant, or otherwise guarantee, expressly or impliedly, the merchantability, fitness for a particular purpose, freedom from patent
infringement, suitability, accuracy, reliability, or completeness of this information or the products, materials or processes described.
Page 33
Table 10: Alliance Intelligent Battery Series™
Multi-Module Faults
Event
Condition
Module Select Disagreement
Inter-module pre-charge ID mismatch
Module Connect Fault
One or more permitted modules failed to pre-charge
or join bus
Module MIA
One or more inter-module critical messages missing
(see inter-module data section)
Module Imbalance
Difference in voltage too great to join bus
Integrated Battery Protection
The Alliance Intelligent Battery Series™ battery technology includes integrated
protection circuitry to prevent the battery from certain damaging use conditions. The
battery’s circuitry interrupts either charging or discharging current if the battery is in
danger of exceeding limits to voltage, current, temperature or internal failure of the
BMS.
Transient Energy Limit
The battery is designed to protect itself from transient voltage spikes which contain
excess energy of up to 2.5 Joules. Inductance, inherent in the cabling used to
connect to the battery and the system, stores energy which can be released
suddenly when the battery protection circuit opens. When this occurs, the passive
energy stored in the wiring and active sources like power supplies and battery
chargers can create large transient spikes, that if exceed 2.5 Joules, can permanently
damage the BMS.
While the product has been designed to handle a maximum inductance
of 10 μH
and
tolerate connections to most power supplies, the user is responsible for ensuring that
the battery does not experience over-voltage surge energy in excess of 2.5 Joules
when conduction is interrupted. External energy absorption devices like capacitors or
clamps can reduce the overshoot or stress on the battery and may be required based
on the application. Please contact American Battery Solutions if you have any
concerns or questions regarding Transient Energy and your specific application and
connection.