Table 2 Converter Failure and Grid System Error Code Descriptions
Code
Cause
Description
Troubleshooting instructions
Er00
DC_BUS charging error
During the converter DC turn-on
procedure, DC_BUS has failed to
reach the preset value
1. Disconnect the solar panel array
and the AC grid from the converter.
2. Wait for all LEDs to be completely
off, and then re-connect the solar
panel array and the AC grid to the
converter.
3. If the error continues to occur,
please contact the supplier.
Er07
DC_BUS voltage too
high
DC_BUS operating voltage higher
than the preset value
Er08
DC_BUS voltage too low
DC_BUS operating voltage lower
than the preset value
Er17
Main control board
memory error
Controller configuration value
error
Er22
Output relay error
Relay error during the converter
AC turn-on procedure
Er24
Output
current
detection error
Output current error during the
converter DC turn-on procedure
Er25
Maximum power point
tracker
A
input
overcurrent
Maximum power point tracker
input current over the rated value
Er26
Maximum power point
tracker
B
input
overcurrent
Er45
Maximum power point
tracker
C
input
overcurrent
Er46
Maximum power point
tracker
D
input
overcurrent
Er48
Converter driver error
Converter IGBT error
Disconnect the solar panel array and
the AC grid from the converter.
Please contact the supplier.
Er49
Converter
driver
overcurrent
Converter output current over the
rated value
Er50
Converter driver voltage
insufficient
Converter IGBT error or current
error
Er51
Maximum power point
track A&B driver error
Maximum power point track IGBT
error
Disconnect the solar panel array and
the AC grid from the converter.
Please contact the supplier.
Er52
Maximum power point
tracker C&D driver error
Er53
Maximum power point
tracker A&B driving
voltage insufficient
Maximum power point tracker
IGBT error or current error
Er54
Maximum power point
tracker C&D driving
voltage insufficient
Summary of Contents for EnerSolis Series
Page 1: ...Ablerex Grid Connected Solar Converter EnerSolis Series ES 52000HC ES 60000HC User Manual ...
Page 4: ...3 ...
Page 9: ...8 8 AC output Transmits AC power generated from the inverter to the mains ...
Page 16: ...15 抓握處 Handles ...
Page 24: ...23 Figure 2 ...
Page 27: ...26 Figure 6 Figure 4 Figure 5 ...
Page 42: ...41 ...
Page 49: ...48 the RS485 port of the cloud module please refer to 6 1 Communication Interface ...
Page 51: ...50 ...
Page 54: ...53 ...
Page 56: ...55 ...
Page 60: ...59 confirm whether there is an input error ...