71
Er09
Converter AC output
overcurrent
Converter AC output current over
the rated value
1. Switch the grid connection circuit
breaker to the “OFF” position, and
inspect the grid system structure.
2. If the grid system is normal and
the error continues to occur, please
contact the supplier.
Er11
Converter overload
Converter AC output power over
the rated value
1. Switch the grid connection circuit
breaker to the “OFF” position, and
inspect the grid system structure.
2. If the grid system is normal and
the error continues to occur, please
contact the supplier.
Er13
Combined
hardware
protection
Converter combined error
Er14
Converter phase locking
error
Failure to synchronize with grid
phase during the converter AC
turn-on procedure
Er29
Converter AC output DC
ratio too high
AC output DC ratio above the
rated value
Er18
Radiating
fin
overheated
Radiating fin overtemperature
1. Lower the ambient temperature of
the converter or relocate the
converter to a well-vented location.
2. If the error continues to occur,
please contact the supplier.
Er02
Auxiliary MCU error
Auxiliary MCU error
If the error continues to occur, please
contact the supplier.
Er12
DC BUS charging failed
DC BUS charging failed
Er43
Output DC ADC failure
Output current sensor failure
Er37
Fan failure
Fan rotation error
1. Check if there is any foreign object
in the fan.
2. If the error continues to occur,
please contact the supplier.
Er55
Exterior fan (model 1)
error
Fan rotation error
Er56
Exterior fan (model 2)
error
Fan rotation error
Er57
Internal cable routing
signal error
Loose cable routing
Disconnect the solar panel array and
the AC grid from the converter.
Please contact the supplier.
Summary of Contents for EnerSolis Series
Page 1: ...Ablerex Grid Connected Solar Converter EnerSolis Series ES 52000HC ES 60000HC User Manual ...
Page 4: ...3 ...
Page 9: ...8 8 AC output Transmits AC power generated from the inverter to the mains ...
Page 16: ...15 抓握處 Handles ...
Page 24: ...23 Figure 2 ...
Page 27: ...26 Figure 6 Figure 4 Figure 5 ...
Page 42: ...41 ...
Page 49: ...48 the RS485 port of the cloud module please refer to 6 1 Communication Interface ...
Page 51: ...50 ...
Page 54: ...53 ...
Page 56: ...55 ...
Page 60: ...59 confirm whether there is an input error ...