3.7.2
Equipment Grounding Installation Procedures
Step 1: Prior to installing the converter grounding, switch the DC input
switch to
0
, and switch the grid-connecting circuit breaker to open
circuit.
Step 2: Please select the 5.5 - 8.0mm2 ground wires, loosen the
equipment’s protective earth (PE) thread locknut, push the wires
through the water-proof plug, enter the wires in the copper pillar
screw hole on the right-hand side of the converter, and secure the
wires. 3.0 Nm torque must be applied on M5 screws for proper
tightening, as shown in Figures 1 and 2.
Figure 1
Step 3: Tighten the equipment’s PE thread locknut; 3 Nm torque must be
applied for proper tightening. The installation is thus completed, as
shown in Figure 7.