1.4 Smart Winter mode
Functionality
Turn pumps on when ambient temperature is below 68°F (20°C)*
Duration
Pumps activate for 1 minute (every 2 hours or less) for at least 24 hours.
Logo or arrow
Filter arrow or logo blinks.
Note: All pumps and blower outputs are activated for 1 minute at various time intervals based on ambient temp.
When the smart winter mode is starting the pumps don’t start all at the same time. Here the sequence follows:
2 first seconds:
Pump #1 Low and circulation pump is starting.
After 2 seconds:
Pump #1 is changing speed and goes to high speed.
After 4 seconds:
Pump #2 is starting to Low speed.
After 6 seconds:
Pump #2 is changing speed and goes to high speed.
After 1 minute:
All other pumps are stopping and pump #3 is starting.
Note: If a key is pressed during a 1 minute cycle, the cycle will be cancelled.
1.5 Power-up detection
Functionality
After a power up, the display will blink until somebody presses a key. This feature is to let
the user know that a power failure has occurred.
Duration
Until key is pressed.
Logo or arrow
Display will blink.
1.6 Inverted display
Functionality
Hold Filter key for 5 seconds and the display will invert.
Reset
At power up display defaults to the non-inverted mode.
Note: In the inverted mode, some icons (ie. F and C) are not displayed.
1.7 Temperature displayed in Fahrenheit or Celsius
Functionality
Hold light key for 5 seconds and the temperature unit will toggle between F and C.
Reset
At power up display defaults to the non-inverted mode F.
45
PA C I F I C H O T T U B S O W N E R ’ S M A N U A L
Summary of Contents for Pacific 2004
Page 54: ...55 PACIFIC HOT TUBS OWNER S MANUAL PHT 1000 PHT 2002 ...
Page 55: ...56 PACIFIC HOT TUBS OWNER S MANUAL PHT 1000 PHT 2002 ...
Page 56: ...57 PACIFIC HOT TUBS OWNER S MANUAL LXT Models equipped with Aqua Stealth ...
Page 57: ...58 PACIFIC HOT TUBS OWNER S MANUAL LXT Models ...
Page 58: ...59 PACIFIC HOT TUBS OWNER S MANUAL ULXT Model ...