56
EN
Parameter
Number
Parameter
Name
Value Range
Unit
Factory
Default
P5-27
Motor Overload
Protection Time
0.1~60.0
min
2.0
P5-28
Threshold for
Motor Overload
Protection
100~160
%
150
P5-29
Function at Mains
Phase Loss
0
:
No Action; 1
:
Only Waring
2
:
Trip to stop and Alarm Fault (Heavy Load)
3
:
Trip to stop and Alarm Fault (Mid Load
)
4
:
Trip to stop and Alarm Fault (Light Load
)
3
P5-30
Alarm/Fault Lock
Handling
0
:
Not Lock, Alarm/Fault Resettable without
Re-Power On
1
:
Lock, Alarm/Fault Lock Resettable only after
Re-Power On
1
P5-31
Delay Time to
Alarm Current
Limit Fault
0~60
s
60
P5-32
Delay Time to
Alarm Torque
Limit Fault
0~60
s
60
P5-33
Action at Warning
0
:
Trip to stop and Alarm Fault directly
1
:
Warning and Re-catch Motor after Failure
Disappear
1
P5-34
Method to Re-catch
Motor at Warning
0
:
Speed Track
(
IM/PM
)
and Angle Track (Fly
start)
1
:
Direct Re-catch
0
P5-60
Selection of
unloading detection
function
0: invalid
1; valid
0
P5-61
Unloading
detection threshold
0.1~200.0%
%
5
P5-62
Off-load detection
filtering time
0.1~600.0
S
1
Parameter Group 6: Keypad Operation and Display
P6-03
Customer Defined
Value for 0 Speed
0.0~6553.5
0.0
P6-04
Customer Defined
Value for Max
Speed
0.0~6553.5
100.0
P6-05
Keypad Display
Option
0~8191
0
P6-31
Local / Remote
Mode Selection
0
:
Remote Mode
1
:
Local Mode
0
P6-32
Free key function
Selection
0
:
Disabled
1
:
Reverse RUN
0
P6-34
Lock Keypad for
Parameter Edit
0
:
Disabled
1
:
Enabled and Lock
0
P6-35
Panel adjustment
frequency step
setting
0
:
0.1
1
:
1.0
2
:
10
Hz
1
P6-50
Motor speed ratio
0.01~655.35
1.00
*P6-51
Current display
compensation.
0.01~655.35
1
*P6-52
Power display
compensation
0.01~655.35
1
Parameter Group 7: Auxiliary and Special Functions
P7-00
Special Operation
Function
0
:
No Function
9
:
Reset Parameters to Factory Defaults
0
Summary of Contents for PU00
Page 3: ...1 CU PU AD800 1 AD800 PU CU 2 4 22kW 15 30kW R S T R L S T N U V W P1 13 1 2...
Page 6: ...4 PU00 30 45kW PU00 55kW 90kW PU00 110 500kW...
Page 9: ...7 1 FWD REV 2 FWD REV...
Page 35: ...33 EN PU00 30 45kW PU00 55kW 90kW PU00 110kW 500kW...
Page 63: ...61 RU 1 PU AD800 CU 2 22kW 4 30kW 15 R S T R L S T N U V W P1 13 1 2 CU C PU AD800...
Page 66: ...64 RU PU00 55 90 PU00 110 500 PU00 560 630...
Page 69: ...67 RU 1 DI FWD DI REV 2 FWD REV 1 DI FWD REV DI1...
Page 70: ...68 RU 2 DI FWD DI REV DI DI1 5 2 2 1 AI1 0 10 AI1 A 2 P0 11 5 DI4 P2 10 40 DI4 3 DI DI...
Page 73: ...71 RU PID PID P4 07 P4 08 5 5 Modbus 1 P0 80 P 0 82 P0 80 1 P0 81 9600 P0 82 2 9999 10000...
Page 95: ...P0100946 V5 1 2022 11 08...