55
EN
Parameter
Number
Parameter Name
Value Range
Unit
Factory
Default
P5-05
Torque Limit at Generator
Mode
0~1000
%
160
P5-06
Source Selection for Speed
Limit at Torque Mode
0
:
No Function
1
:
Input From Terminal AI1
2
:
Input From Terminal AI1
5
:
Pulse Input 1
10: Preset Value 0 + UP/DOWN
11: Preset Value
20
:
Bus Communication
30
:
Keypad
0
P5-07
Max Current Limit
0~300
%
*
*P5-08
Max Output Frequency
Limit
0.0~590.0
Hz
65.0
P5-09
Threshold for Low Current
Warning
0.00~P9-16
A
0.0
P5-10
Threshold for High Current
Warning
0.00~P9-16
A
*
P5-11
Threshold for Low Speed
Warning
0.0~590.0
Hz
0.0
P5-12
Threshold for High Speed
Warning
0.1~590.0
Hz
65.0
P5-13
Threshold for Low Set
Value Warning
-200.00~200.00
%
0.00
P5-14
Threshold for High Set
Value Warning
-200.00~200.00
%
100.00
P5-15
Threshold for Low
Feedback Warning
-200.00~200.00
%
0.00
P5-16
Threshold for High
Feedback Warning
-200.00~200.00
%
100.00
*P5-17
Enable Motor Phase Loss
Protection
0: off.
1: low sensitivity detection 2: high
sensitivity detection
1
P5-18
Enable Current
Limit/Torque Limit
Warning
0
:
Disable
1
:
Enable
1
P5-19
Motor Speed Feedback Loss
Function
0
:
No Function
3
:
Jog and Warning
4
:
Run to Max Speed P5-03 and Warning
5
:
Alarm Fault and Trip to stop
11
:
Switch to Speed Sensor less Mode
5
P5-20
Speed Error for Speed
Feedback Loss Detection
1 ~ 6000
rpm
300
P5-21
Time for Speed Feedback
Loss Detection
0.00 ~ 60.00
s
2
P5-22
Threshold for
Communication with CU
Timeout
0.10~60.00
s
1.00
P5-23
Communication with CU
Timeout Function
0
:
No Function
2
:
Stop and Warning
3
:
Jog and Warning
4
:
Run to Max Speed P5-03 and Warning
5
:
Alarm Fault and Trip to stop
6
:
Warning
5
P5-26
Motor Thermal Protection
Function
0
:
No Function;
1
:
ETR Warning
2
:
ETR Alarm Fault
3
:
ETR Warning for Self-cooled Motor
4
:
ETR Alarm Fault for Self-cooled Motor
0
Summary of Contents for PU00
Page 3: ...1 CU PU AD800 1 AD800 PU CU 2 4 22kW 15 30kW R S T R L S T N U V W P1 13 1 2...
Page 6: ...4 PU00 30 45kW PU00 55kW 90kW PU00 110 500kW...
Page 9: ...7 1 FWD REV 2 FWD REV...
Page 35: ...33 EN PU00 30 45kW PU00 55kW 90kW PU00 110kW 500kW...
Page 63: ...61 RU 1 PU AD800 CU 2 22kW 4 30kW 15 R S T R L S T N U V W P1 13 1 2 CU C PU AD800...
Page 66: ...64 RU PU00 55 90 PU00 110 500 PU00 560 630...
Page 69: ...67 RU 1 DI FWD DI REV 2 FWD REV 1 DI FWD REV DI1...
Page 70: ...68 RU 2 DI FWD DI REV DI DI1 5 2 2 1 AI1 0 10 AI1 A 2 P0 11 5 DI4 P2 10 40 DI4 3 DI DI...
Page 73: ...71 RU PID PID P4 07 P4 08 5 5 Modbus 1 P0 80 P 0 82 P0 80 1 P0 81 9600 P0 82 2 9999 10000...
Page 95: ...P0100946 V5 1 2022 11 08...