60
EN
Parameter
Number
Parameter Name
Value Range
Unit
Factory
Default
Parameter Group 20
:
Pump
P20-00
pump control mode
0: pressure mode
3: photovoltaic pump mode
0
P20-01
minimum output frequency
0.00~P20-02
%
40
P20-02
maximum output frequency
P20-01~100.00
%
100
P20-60
Sleep enable selection
0
:
disable; 1
:
enable
0
P20-61
Sleep frequency threshold
0.00~100.00
%
2
P20-62
Sleep pressure threshold
0.00~100.00
%
2
P20-63
Sleep detection time
0.0~300.0
S
10
P20-64
minimum sleep time
0.0~1800.0
S
300
P20-65
wake up pressure threshold
0.00~100.00
%
10
P20-66
wake up detection time
0.0~60.0
S
1