5.2.1. Start-stop control
Single-wire pulse start/stop
Enable the Pulse Auto Start/Stop Function by set P2-03=1 first then define a terminal function to Pulse
Run (DI function 13 or 14). With below wiring, the single wire pulse start/stop function can be
achieved.
Two-wires mode 1 (factory default)
The DI terminal FWD is default to forward run function, and the DI terminal REV is default to reverse
run function. You can achieve the two wires start/stop function by Wiring and parameters set as below.
Two-wires mode 2
In this mode, the FWD terminal is to start/stop the motor, the REV terminal is to control the running
direction. The function can work with Wiring and parameters set as below.
Three-wire mode 1
The DI terminals FWD and REV are used to start the motor by pulse for different direction, the DI1
terminal is used to stop the motor. The function can be achieved by wiring and parameter set as below.
Summary of Contents for PU00
Page 3: ...1 CU PU AD800 1 AD800 PU CU 2 4 22kW 15 30kW R S T R L S T N U V W P1 13 1 2...
Page 6: ...4 PU00 30 45kW PU00 55kW 90kW PU00 110 500kW...
Page 9: ...7 1 FWD REV 2 FWD REV...
Page 35: ...33 EN PU00 30 45kW PU00 55kW 90kW PU00 110kW 500kW...
Page 63: ...61 RU 1 PU AD800 CU 2 22kW 4 30kW 15 R S T R L S T N U V W P1 13 1 2 CU C PU AD800...
Page 66: ...64 RU PU00 55 90 PU00 110 500 PU00 560 630...
Page 69: ...67 RU 1 DI FWD DI REV 2 FWD REV 1 DI FWD REV DI1...
Page 70: ...68 RU 2 DI FWD DI REV DI DI1 5 2 2 1 AI1 0 10 AI1 A 2 P0 11 5 DI4 P2 10 40 DI4 3 DI DI...
Page 73: ...71 RU PID PID P4 07 P4 08 5 5 Modbus 1 P0 80 P 0 82 P0 80 1 P0 81 9600 P0 82 2 9999 10000...
Page 95: ...P0100946 V5 1 2022 11 08...