37
EN
Three-wires mode 2
The DI terminal FWD is used to start the motor by pulse, DI terminal REV is used to control the motor
direction, DI terminal DI1 is used to stop the motor. The function can be achieved by wiring and
parameters set as below.
5.2.2. Target Speed Set
In remote mode, both analogue input AI1 and bus communication are default for speed set. By
applying an 0 ~ 10V on terminal AI1 and/or controlling command from the bus communication
can adjust the speed set. Please refer to the appendix A for more details about bus
communication control.
Use pulse input for speed set: Define the main speed set source as pulse input (P0-11 = 5), and
define the terminal function of DI4 to pulse input (P2-10 = 40), then you can adjust the speed
set by applying different frequency of pulse on DI4. Using pulse input for speed set has the
advantages of good accuracy and robust to EMC noise.
Multi preset value control by DI terminal function.In some application, the motor only needs to
run at several fixed speed. You can use DI terminal function to control the motor speed at
different preset value. Below is an example of 16 preset speed controlled by 4 DI terminals.
Summary of Contents for PU00
Page 3: ...1 CU PU AD800 1 AD800 PU CU 2 4 22kW 15 30kW R S T R L S T N U V W P1 13 1 2...
Page 6: ...4 PU00 30 45kW PU00 55kW 90kW PU00 110 500kW...
Page 9: ...7 1 FWD REV 2 FWD REV...
Page 35: ...33 EN PU00 30 45kW PU00 55kW 90kW PU00 110kW 500kW...
Page 63: ...61 RU 1 PU AD800 CU 2 22kW 4 30kW 15 R S T R L S T N U V W P1 13 1 2 CU C PU AD800...
Page 66: ...64 RU PU00 55 90 PU00 110 500 PU00 560 630...
Page 69: ...67 RU 1 DI FWD DI REV 2 FWD REV 1 DI FWD REV DI1...
Page 70: ...68 RU 2 DI FWD DI REV DI DI1 5 2 2 1 AI1 0 10 AI1 A 2 P0 11 5 DI4 P2 10 40 DI4 3 DI DI...
Page 73: ...71 RU PID PID P4 07 P4 08 5 5 Modbus 1 P0 80 P 0 82 P0 80 1 P0 81 9600 P0 82 2 9999 10000...
Page 95: ...P0100946 V5 1 2022 11 08...