2104349 rev. AD
Page 31
6.2.9.2
Digital/Pulse Points
The DI/PI inputs will accept NAMUR type sensor inputs which meet the IEC-
60947-5-6 electrical characteristics. The digital inputs also function as event
counters.
Digital Outputs
-
Optically-isolated type 1A switches
-
Have a maximum ON resistance of 2.5
Ω which can switch 48V AC/DC at up
to 200 mA at 60°C
-
The outputs are isolated (AC voltage for 1 minute at 25°C, RH=60%
between input and output) from each other as well as the control circuit by
1500Vrms
The digital inputs must be defined in PCCU32.