Troubleshooting
This section discusses a few potential issues during the initial startup of the flow computer.
The LCD displays alarm conditions and status codes in the Annunciator area, see
IMPORTANT NOTE:
Alarms are recorded in the Log period flow record. Status codes are not
recorded in the Log period flow record.
Figure 12-1: XSeries
G5
annunciators
The following table lists the indicator symbol and description of the status and alarm codes.
Table 12-1: XSeries
G5
status and alarm codes
Indicator
Description
System
LL
Low Lithium Battery Alarm: When LL (low lithium) is displayed, the lithium battery
voltage is below 2.5 Vdc. A new lithium battery measures approximately 3.6 Vdc.
LC
Low Charger: When LC (low charger) is displayed, the XSeries
G5
battery charging
voltage is (+) 0.4 Vdc, or is less than or equal to the battery voltage.
Communication Protocols
Transmitting Data: Sending a response
Receiving Data: Processing request
Nak: Negative acknowledgement with packet list
+
Ack: Positive acknowledgement of receipt of request
Waiting for Ack: Waiting for response after transmission
Exception Alarm Processing
ID Recognized: Recognized and receiving request
Listen Cycle: Flashes if this remote port is active and running Totalflow Remote
Protocol. Flashes in sync with the listening cycle that occurs at 1, 2 or 4 second
intervals. When the baud rate is faster than 2400, then the flashing symbol may not be
visible. The annunciator will remain on listening cycle if the listen cycle is set to zero.
M
MODBUS
®
ASCII: MODBUS
®
ASCII protocol is selected for the port assigned to this
annunciator.
m
MODBUS
®
RTU: MODBUS
®
RTU protocol is selected for the port assigned to this
annunciator.
L
Local Protocol: Displayed when the PCCU32 port is active and running Totalflow Local
Protocol
¥
ID Recognized: The recognized ID is waiting for sync.
u
USB Protocol: Displayed when the USB port is active and running Totalflow Remote
n
Ethernet Protocol: Displayed when the Totalflow/TCP port is active.
Battery Voltage
14.3 VOLTS
A
D
L
C
L
Annunciators
A1
A2
A7
A8