4 Installation in the transformer
4.1 Tools
Tool
Part number
Note
Air pump with pressure gauge and
hose
-
Pressure range 0-250 kPa, hose
connection with internal thread
R 1/8”.
Standard set of open-end
wrenches
-
Up to 18 mm.
Standard set of socket wrenches
-
Up to 18 mm.
Socket wrench extender
-
-
Standard set of screwdrivers
-
-
Hex keys
-
5 mm and 6 mm.
Hand crank
LL 117 016-M
Ordered separately.
Torque wrench
-
5-85 Nm, tolerance ≤ 10 %.
Buzzer
-
For testing the pressure relay.
500 V DC power unit/insulation
tester
-
For testing the pressure relay.
Bottom valve key
LL 117 016-A
Supplied with the tap-changer.
Tool for opening oil drum
-
-
Hacksaw
-
-
Bucket
-
10 liters
Soft lifting slings
-
Rated for a weight higher than the
combined weight of the
tap-changer and transport box.
Lifting chains
-
Rated for a weight higher than the
combined weight of the
tap-changer and transport box.
Crane
-
Rated for a weight higher than the
combined weight of the
tap-changer and transport box.
Equipment for oil filling
-
-
Soft bedding
-
Particleboard, thick rubber-mat or
equivalent.
Summary of Contents for VUBB
Page 14: ...14 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 28: ...28 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 52: ...52 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 60: ...60 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 68: ...68 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 72: ...72 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 74: ...74 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 76: ...76 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...