Technical data
24
Technical data
41/18-77 EN
4
Technical data
4.1 Basic model
Communication
Profiles
Profibus PA Profile for Process Control Devices
Electro Pneumatic Actuator V3.0
Block types
1 AO Function Block, 1 Transducer Block,1 Physical Block
Physical layer
Compliant to the standard IEC 61158-2
Communication speed
31.25 Kbit/second
Operating voltage
Bus-powered: 9.0 - 32.0 volts
Max. withstand voltage
35 V
Current consumption
10.5 mA
Fault current
15 mA (10.5 mA + 4.5 mA)
Name
Physical device tag
TZID-C110
PNO ID number
0x0639
Device ID
0X3200028xyz
Device address
Between 0 and 126, default node address 126
Output
Range
0...6 bar (0...90 psi)
Air capacity
at supply pressure of 1.4 bar (20 psi)
5.0 kg/h = 3.9 Nm
3
/h = 2.3 scfm
at supply pressure of 6 bar (90 psi)
13 kg/h = 10 Nm
3
/h = 6.0 scfm
(Booster, for increasing air capacity, on request)