Installing and commissioning
4
Installing and commissioning
41/18-77 EN
3
Installing and commissioning
3.1 Mechanical mounting
3.1.1 General
The arrow (1) on the feedback
shaft (and thus the lever) must
travel within the area marked with
the small arrows (2).
When mounting,
ensure that the
transfer of the
stroke or rotation
angle for the posi-
tion feedback is
correct. The maxi-
mum rotation
angle is 60° for
mounting to linear
actuators and
120° for mounting
to rotary actua-
tors. The mini-
mum range for
both applications
is 25°.
Fig. 1
Operating range
1
2
TZID-C
+60°
-60°
+30°
-30°
100%
0%
100%
0%
Sensor range for rotary actuators
Stroke range
Valve range
Sensor range for linear actuators
Fig. 2
Positioner ranges