58 94-1100-00002874 A0 EN│TruFit™ Power Distribution Unit
Table 5-1 shows the defaults and the minimum and maximum set point values that can be set using the
PDU Configuration Limit screen above.
Table 5-1: PDU alarm/warning limit settings
Description
Min
Default
Max
Units
Input OV Alarm Limit
115
115
125
%
Input OV Warning Limit
105
110
115
%
Input UV Warning Limit
85
95
95
%
Input UV Alarm Limit
75
85
85
%
Output OV Alarm Limit
115
115
125
%
Output OV Warning Limit
105
110
115
%
Output UV Warning Limit
85
95
95
%
Output UV Alarm Limit
75
85
85
%
Output OC Alarm Limit
125
125
150
%
Output OC Warning Limit
100
115
125
%
Neutral Current Limit
0.1
125
150
%
Ground Current Limit
5
20
50
A
Frequency
0.1
0.5
4
Hz