INSTALLATION INSTRUCTIONS

Original Issue Date:

12/16

Model:

KD Series Generator Sets with APM802 Controller

Market:

Industrial

Subject:

Remote Emergency Stop Kits, 11101000201-KP1

Introduction

TP-6200

Figure 1

Remote Emergency Stop Switch

The emergency stop kit allows immediate shutdown of

the generator set from a remote location. Mount the

emergency stop switch(es) in a location easily

accessible by operating personnel at a normal

workstation. See Figure 1.

If the emergency stop switch is activated, the controller

shuts down the unit, places the controller in

Out-of-Service

mode, and displays an Emergency

Push Button Engaged Fault on the HMI. The generator

set cannot be restarted until the emergency stop

switch(es) is reset by replacing the glass piece and

clearing the fault on the controller.

Emergency Stop Kit Connection

(with multiple switches)

Emergency Stop

Kit Connection

(with single switch)

TB10

terminal

block

Remove jumper before

installing kit.

1

2

1

2

1

2

1

2

K10

K10 relay

Local Emergency Stop

Figure 2

Terminal Block Connections

Connect as many emergency stop switches as

required; however, connect multiple switches in

series

so the system functions correctly. The emergency stop

switch is connected to terminal block 10, TB10-1 and 2.

See Figure 2. Remove the jumper from terminals

TB10-1 and 2 before installing the kit. When the

emergency stop switch is activated, contacts in the

switch open to deenergize the K10 relay and shut down

the generator set.

Summary of Contents for Power Systems KD Series

Page 1: ...ed Fault on the HMI The generator set cannot be restarted until the emergency stop switch es is reset by replacing the glass piece and clearing the fault on the controller Emergency Stop Kit Connection with multiple switches Emergency Stop Kit Connection with single switch TB10 terminal block Remove jumper before installing kit 1 2 1 2 1 2 1 2 K10 K10 relay Local Emergency Stop Figure 2 Terminal B...

Page 2: ... the battery Follow these precautions to prevent the starting of the generator set by the remote start stop switch Hazardous voltage Will cause severe injury or death Disconnect all power sources before opening the enclosure DANGER Installation Procedure 1 Before working on the generator set or connected equipment disable the generator set Refer to the safety precautions for preventing accidental ...

Page 3: ...e back of the control panel to the terminal strip TB10 See Figure 3 Cut leads to length strip the ends and connect to terminals TB10 1 and 2 See Figure 2 8 Position and secure the lower compartment cover 9 Check that the generator set is in Out of Service mode 10 Reconnect the generator set engine starting battery negative lead last 11 Reconnect power to the battery charger Resetting Procedure 1 R...

Page 4: ...er Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone 65 6264 6422 Fax 65 6264 6455 Availability is subject to change without notice Kohler Co reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever Contact your local Kohlerr generator set distributor for availability 2016 by Kohler Co All rights reserved ...

Reviews: