TT-1719 12/16

Safety Precautions

Observe the following safety precautions while

installing the kit.

Accidental starting.

Can cause severe injury or death.

Disconnect the battery cables before

working on the generator set.

Remove the negative (--) lead first

when disconnecting the battery.

Reconnect the negative (--) lead last

when reconnecting the battery.

WARNING

Disabling the generator set. Accidental starting can

cause severe injury or death.

Before working on the

generator set or equipment connected to the set, disable the

generator set as follows: (1) Shut down the generator set. (2)

Place the controller in Out of Service mode. (3) Press the

emergency stop button. (4) Disconnect the power to the

battery charger, if equipped. (5) Remove the battery cables,

negative (--) lead first. Reconnect the negative (--) lead last

when reconnecting the battery. Follow these precautions to

prevent the starting of the generator set by the remote

start/stop switch.

Hazardous voltage.

Will cause severe injury or death.

Disconnect all power sources before

opening the enclosure.

DANGER

Installation Procedure

1. Before working on the generator set or connected

equipment, disable the generator set. Refer to the

safety precautions for preventing accidental starts

and disabling the generator set.

a. Remove the load from the generator set.

b. Shut down the generator set.

c. Place the generator set controller into

Out-of-Service

mode

and

press

the

emergency stop button.

d. Disconnect the power to the battery charger.

e. Remove the battery cables negative (--) lead

first to disable the generator set.

2. To access the terminal block, TB10, remove the

eight screws from the lower compartment cover on

the control panel. See Figure 3.

3. Remove jumper from terminals TB10-1 and 2.

1. Lower compartment

cover

2. TB10

3. 38 mm (1-1/2 in.) holes

1

2

3

Figure 3

Lower Compartment Component Location

Summary of Contents for Power Systems KD Series

Page 1: ...ed Fault on the HMI The generator set cannot be restarted until the emergency stop switch es is reset by replacing the glass piece and clearing the fault on the controller Emergency Stop Kit Connection with multiple switches Emergency Stop Kit Connection with single switch TB10 terminal block Remove jumper before installing kit 1 2 1 2 1 2 1 2 K10 K10 relay Local Emergency Stop Figure 2 Terminal B...

Page 2: ... the battery Follow these precautions to prevent the starting of the generator set by the remote start stop switch Hazardous voltage Will cause severe injury or death Disconnect all power sources before opening the enclosure DANGER Installation Procedure 1 Before working on the generator set or connected equipment disable the generator set Refer to the safety precautions for preventing accidental ...

Page 3: ...e back of the control panel to the terminal strip TB10 See Figure 3 Cut leads to length strip the ends and connect to terminals TB10 1 and 2 See Figure 2 8 Position and secure the lower compartment cover 9 Check that the generator set is in Out of Service mode 10 Reconnect the generator set engine starting battery negative lead last 11 Reconnect power to the battery charger Resetting Procedure 1 R...

Page 4: ...er Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone 65 6264 6422 Fax 65 6264 6455 Availability is subject to change without notice Kohler Co reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever Contact your local Kohlerr generator set distributor for availability 2016 by Kohler Co All rights reserved ...

Reviews: