TT-1719 12/16

3

4. Verify that the emergency stop switch leads are

from the normally closed contacts. Use an

ohmmeter to perform the continuity test. Use tape

to insulate the normally open contact leads as they

will not be used.

5. Determine the approximate mounting location(s)

for the emergency stop switch(es) and cut two

lengths of 16-gauge (minimum) stranded wire long

enough to connect the controller and switch(es).

Strip one end of each wire length and connect to

switch leads using wire nuts (not supplied).

Connect the two white leads from the switch to the

lead from terminal 1. Connect the two black leads

from the switch to the lead from terminal 2.

6. Mount emergency stop switch(es) in desired

location(s). Use #6 round head wood screws (not

supplied). Use supplied machine screws when

mounting in a single-gang electrical box.

7. Route the stranded wire through the 38 mm

(1-1/2 in.) holes in the back of the control panel to

the terminal strip, TB10. See Figure 3. Cut leads

to length, strip the ends, and connect to terminals

TB10-1 and 2. See Figure 2.

8. Position and secure the lower compartment cover.

9. Check that the generator set is in

Out-of-Service

mode.

10. Reconnect the generator set engine starting

battery, negative (--) lead last.

11. Reconnect power to the battery charger.

Resetting Procedure

1. Replace glass rod on emergency stop switch (an

extra piece of glass is supplied with each switch).

2. Reset the fault displayed on the controller human

machine interface (HMI).

3. Place the generator set into Manual mode for local

starting or to AUTO mode for startup by automatic

transfer switch or remote start switch. Refer to the

controller

operation

manual

for

controller

operation instructions.

Parts List

Qty. Description

Part Number

1

Switch, emergency stop

A-222654

2

Rod, glass*

222655

* Part of A-222654 emergency stop switch. One glass rod is

installed on the switch and an additional replacement glass rod

is located inside the switch. Additional glass rods are available

as a service part.

Summary of Contents for Power Systems KD Series

Page 1: ...ed Fault on the HMI The generator set cannot be restarted until the emergency stop switch es is reset by replacing the glass piece and clearing the fault on the controller Emergency Stop Kit Connection with multiple switches Emergency Stop Kit Connection with single switch TB10 terminal block Remove jumper before installing kit 1 2 1 2 1 2 1 2 K10 K10 relay Local Emergency Stop Figure 2 Terminal B...

Page 2: ... the battery Follow these precautions to prevent the starting of the generator set by the remote start stop switch Hazardous voltage Will cause severe injury or death Disconnect all power sources before opening the enclosure DANGER Installation Procedure 1 Before working on the generator set or connected equipment disable the generator set Refer to the safety precautions for preventing accidental ...

Page 3: ...e back of the control panel to the terminal strip TB10 See Figure 3 Cut leads to length strip the ends and connect to terminals TB10 1 and 2 See Figure 2 8 Position and secure the lower compartment cover 9 Check that the generator set is in Out of Service mode 10 Reconnect the generator set engine starting battery negative lead last 11 Reconnect power to the battery charger Resetting Procedure 1 R...

Page 4: ...er Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone 65 6264 6422 Fax 65 6264 6455 Availability is subject to change without notice Kohler Co reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever Contact your local Kohlerr generator set distributor for availability 2016 by Kohler Co All rights reserved ...

Reviews: