TruFit™
Power Distribution Unit│94-1100-00002874 A0 EN 21
3.4.2
Protocol Settings screen
The Protocol Settings screen is used to configure the upstream access parameters.
E.g.: SSH (Secured Shell), Modbus TCP, Modbus RTU & TFTP settings.
Figure 3-9: Protocol Settings screen
3.4.2.1
Modbus TCP configuration:
Figure 3-10: Modbus TCP configuration
Modbus TCP can be configured from this tile.
The on/off toggle slider is used to enable/disable this feature.
IP1 & IP2 are the IP address of the polling device.
o
If IP1 & IP2 are 0.0.0.0 any device can poll
o
If either IP1/IP2 is set, only the IP address that is entered can poll the unit.
ego: If IP1 is 192.168.5.4 & IP2 is 0.0.0.0 only IP1 can poll the device.