6 94-1100-00002874 A0 EN│TruFit™ Power Distribution Unit
Installation
- This PDU must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the PDU, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the PDU, make sure that all earth connections when reassembling, are
correctly reattached.
- This PDU is intended for use in a controlled indoor environment free of conductive contaminants and
protected against animal intrusion.
- WARNING! HIGH LEAKAGE CURRENT TO GROUND:
Ground connection is essential before connecting to AC input!
- Switching OFF the Unit does not isolate the PDU from the Utility.
- Do not install the PDU in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the PDU.
- The Unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed
104
F (40°C).
- It is important that air can move freely around and through the Unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
Storage
- Store the PDU in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55
C).