WBPEEUI240751C0
PR34 - 1
PR34
RLY-200 Relay Replacement
Purpose/Scope
This procedure gives the steps to replace a relay on the
RLY-200 block.
NOTE:
Check for a blown fuse before replacing a relay.
Parts
Tools
•
Small-tipped, flat-blade screwdriver.
Safety Considerations
Procedure
□
1. Turn off power to the field device controlled by the relay
being replaced.
□
2. Open the access door, then loosen the attachment screw of
the relay to be replaced (Fig.
PR34-1
).
5 min.
Number
Qty
Description
1947684A32
1 - 8
120 VAC solid state relay
1947685A31
24 VDC solid state relay
1947685A32
125 VDC solid state relay
1947803A1
240 VAC solid state relay
WARNING
1. Verify field power is turned off before starting the replace-
ment procedure. Failure to do so could result in severe or fatal
shock. Do not turn the power on until the replacement proce-
dure is complete.
CAUTION
1. Use only ABB Automation approved relays on the relay
assembly. Using unapproved relays could improperly route sig-
nals and damage equipment connected to the relay and the
relay itself. CSA certification is voided when unapproved relays
are used.
W1
Summary of Contents for Symphony Harmony Series
Page 1: ...Instruction Harmony Series HarmonyInput O utput System I O and Auxiliary Blocks ...
Page 129: ...WBPEEUI240751C0 ...
Page 171: ...WBPEEUI240751C0 ...
Page 221: ...WBPEEUI240751C0 ...
Page 227: ...WBPEEUI240751C0 ...
Page 235: ...WBPEEUI240751C0 ...
Page 261: ...WBPEEUI240751C0 ...
Page 267: ...WBPEEUI240751C0 ...
Page 285: ...WBPEEUI240751C0 ...
Page 289: ...WBPEEUI240751C0 ...
Page 293: ...WBPEEUI240751C0 ...
Page 301: ...WBPEEUI240751C0 ...
Page 309: ...WBPEEUI240751C0 ...
Page 319: ...WBPEEUI240751C0 ...
Page 329: ...WBPEEUI240751C0 ...
Page 335: ...WBPEEUI240751C0 ...
Page 341: ...WBPEEUI240751C0 ...
Page 351: ...WBPEEUI240751C0 ...
Page 367: ...WBPEEUI240751C0 ...
Page 377: ...WBPEEUI240751C0 ...
Page 401: ...WBPEEUI240751C0 ...