Procedure
WBPEEUI240751C0
PR11 - 5
□
12. Verify a 3.15 A, 250 V fuse is present in the field power
fuse holder.
□
13. Open the access door of the CIO-100 base and verify a
6.3 A, 250 V fuse is present in fuse holder F1. This fuse is for
the +24 VDC LFP power that operates IISAC01 control sta-
tions. The fuse protects the power distributed to both station
connectors.
NOTE:
If connecting to a CIO-110 block for electric drive/pulse positioner termi-
nation, +24 VDC LFP power to operate the IISAC01 control stations attaches
and is fuse protected at the CIO-110 block instead of at the CIO-100 block.
Figure PR11-1. User-Configurable Jumpers - Base
T 00 9 59 A
J 15
J16
1-J1
1-J3
1-J2
1-J4
2-J1
2-J3
3-J1
3-J3
4-J1
4-J3
2-J2
2-J4
3-J2
3-J4
4-J2
4-J4