I/O Block
WBPEEUI240751C0
3 - 21
Default States
Default states for outputs are selected during function code
configuration. The outputs will automatically return to normal
operation after communication has been restored. For an ana-
log output, the default state is either zero percent output, 100
percent output, or hold the current output. For a digital out-
put, the default state is either zero state output, one state out-
put, or hold the current output. Refer to
Function Codes
Function Codes
Function Codes
Function Codes
in
Section 6 for information about default state specifications.
Failure States
Failure states for outputs are by default their unpowered or off
states. A nonredundant output channel will enter its failure
state when:
•
All power to the I/O module is lost.
•
Machine fault timer error occurs (refer to
Machine Fault
Machine Fault
Machine Fault
Machine Fault
Timer
Timer
Timer
Timer
in this section).
Figure 3-15. Redundant I/O Block
T 00816C
TE R M IN ATIO N BA S E FO R
R E DU NDAN T I/O M O D ULE S
TW O ID E N TIC AL
I/O M O D U LE S
R E D U N DAN T
I/O BLO CK
Summary of Contents for Symphony Harmony Series
Page 1: ...Instruction Harmony Series HarmonyInput O utput System I O and Auxiliary Blocks ...
Page 129: ...WBPEEUI240751C0 ...
Page 171: ...WBPEEUI240751C0 ...
Page 221: ...WBPEEUI240751C0 ...
Page 227: ...WBPEEUI240751C0 ...
Page 235: ...WBPEEUI240751C0 ...
Page 261: ...WBPEEUI240751C0 ...
Page 267: ...WBPEEUI240751C0 ...
Page 285: ...WBPEEUI240751C0 ...
Page 289: ...WBPEEUI240751C0 ...
Page 293: ...WBPEEUI240751C0 ...
Page 301: ...WBPEEUI240751C0 ...
Page 309: ...WBPEEUI240751C0 ...
Page 319: ...WBPEEUI240751C0 ...
Page 329: ...WBPEEUI240751C0 ...
Page 335: ...WBPEEUI240751C0 ...
Page 341: ...WBPEEUI240751C0 ...
Page 351: ...WBPEEUI240751C0 ...
Page 367: ...WBPEEUI240751C0 ...
Page 377: ...WBPEEUI240751C0 ...
Page 401: ...WBPEEUI240751C0 ...