RECORDED AND MEMORIZED PARAMETERS
Current in phase L1 at starting or tripping
V11...V51 R
0...63 x I
n
Current in phase L2 at starting or tripping
V12...V52 R
0...63 x I
n
Current in phase L3 at starting or tripping
V13...V53 R
0...63 x I
n
Netral current Io at starting or tripping
V14...V54 R
0...210 % I
n
Duration of the latest starting
situation of stage I>
V15...V55 R
0...100%
Duration of the latest starting
situation of stage I>>
V16...V56 R
0...100%
Duration of the latest starting
situation of stage I
0
>
V17...V57 R
0...100%
Duration of the latest starting
situation of stage I
0
>>
V18...V58 R
0...100%
Maximum demand current for 15 min.
V1
R
0...2.5 x I
n
Number of startings of stage I>
V2
R
0...255
Number of startings of stage I>>
V3
R
0...255
Number of startings of stage I
0
>
V4
R
0...255
Number of startings of stage I
0
>>
V5
R
0...255
Phase conditions during trip
V6
R
1 = I
L3
>, 2 = I
L2
>,
4 = I
L1
>, 8 = I
0
>
16 = I
L3
>>, 32 = I
L2
>>
64 = I
L1
>>,128 = I
0
>>
Operation indicator
V7
R
0...9
Highest maximum demand current
15 minute value
V8
R
0…2.55 x I
n
CONTROL PARAMETERS
Resetting of output relays
V101
W
1 = output relays and all
at self-holding
information from
the display are reset
Resetting of output relays
V102
W
1 = output relays and
and recorded data
registers are reset
Remote control of settings
V150
R, W
0 = main settings
activated
1 = second settings
activated, see
section "Description
of function"
Event mask word for overcurrent events
V155
R, W
0...255, see section
"Event codes"
Event mask word for earth-fault events
V156
R, W
0...255, see section
"Event codes"
Event mask word for output signal events
V157
R, W
0...1023, see section
"Event codes"
Opening of password for remote settings
V160
W
1...999
Changing or closing of password for
remote settings
V161
W (P)
0...999