15
Remote transfer
data
(modified 2000-02)
memory (V data), output data (O data) and
some other data. Further, part of the data can be
altered by commands given over the SPA bus.
All data are in channel 0.
In addition to the event data, the SPA bus allows
the data communication equipment to read all
input data (I data) of the relay module, setting
values (S values), information recorded in the
Data
Code
Data
Values
direct.
Measured residual voltage value
I1
R
0...25% x U
n
999, if U
0
> 25% x U
n
Measured neutral current value
I2
R
0...100% x I
n
999, if I
0
> 100% x I
n
Measured value I
0
cos
ϕ
or
I3
R
±
0...100% x I
n
I
0
sin
ϕ
(sign +/-)
±
999, if I
ϕ
> 100% x I
n
Blocking of low-set stage I
ϕ
>
I4
R
0 = no blocking
1 = tripping I
ϕ
>-stage
blocked
Blocking of high-set stage I
ϕ
>>
I5
R
0 = no blocking
1 = tripping I
ϕ
>>-stage
blocked
Remote control of the operation
I6
R
0 = I
0
sin
ϕ
characteristic sin
ϕ
/cos
ϕ
1 = I
0
cos
ϕ
Start of low-set stage I
ϕ
>
O1
R
0 = stage I
ϕ
> not started
1 = stage I
ϕ
> started
Tripping of low-set stage I
ϕ
>
O2
R
0 = stage I
ϕ
> not tripped
1 = stage I
ϕ
> tripped
Start of high-set stage I
ϕ
>>
O3
R
0 = stage I
ϕ
>> not started
1 = stage I
ϕ
>> started
Tripping of high-set stage I
ϕ
>>
O4
R
0 = stage I
ϕ
>> not tripped
1 = stage I
ϕ
>> tripped
Active start current I
ϕ
of the low-set
S1
R
1...10% x I
n
stage I
ϕ
>
Active operate time t> of the low-set
S2
R
0.1...10 s
stage I
ϕ
>
Active start current I
ϕ
>> of the high-
S3
R
±
1...40% x I
n
set stage (sign
±
)
±
999 =
∞
Active operate time t>> of the high-
S4
R
0.1...1 s
set stage I
ϕ
>>
Active checksum of selector switch-
S5
R
0...255
group SG1
Start current I
ϕ
of stage I
ϕ
>,
S11
R
1...10% x I
n
set with the setting knob
Operate time t> of stage I
ϕ
>,
S12
R
0.1...10 s
set with the setting knob
Start current of stage I
ϕ
>>, set
S13
R
±
1...40% x I
n
with the setting knob (sign
±
)
±
999 =
∞
Operate time of stage I
ϕ
>>,
S14
R
0.1...1 s
set with the setting knob
Checksum of switchgroup SG1,
S15
R
0...255
set with the selector switches