11
The control module SPTO 6D3 is capable of
indicating status of seven objects (circuit break-
ers or disconnectors) and controlling (opening
or closing) six objects.
The control module suits different circuit
breaker/disconnector/earthing switch configu-
rations within the above mentioned limits. The
configuration can be freely selected by using the
configuration commands explained below. Af-
ter factory testing all indicators are set out of use
and the user must select his own configuration.
The seven input channels 1…7 are used for
reading status data of circuit breakers and
disconnectors. The input channel numbers are
used when the circuit breaker/disconnector con-
figuration is set.
The code numbers of the indicatorm units on
the front panel range from 101...116 and they
are used when the feeder terminal is configured.
The locatio and the code numbers of the indica-
tor units in the matrix are shown in Fig. 6.
The control module has 12 control outputs,
OPEN1…6 and CLOSE1…6 for the control of
six objects. The control outputs have their own
code numbers, 20...31, which have to be used
when the control module is configured. The
output code numbers correspond to the follow-
ing functions:
Output code
Function
number
20
OPEN1
21
CLOSE1
22
OPEN2
23
CLOSE2
24
OPEN3
25
CLOSE3
26
OPEN4
27
CLOSE4
28
OPEN5
29
CLOSE5
30
OPEN6
31
CLOSE6
For the correspondence between the input and
output codes and the terminal numbers on the
rear panel of the feeder terminal see chapter
"Connection diagram" in the user´s manual for
the feeder terminal.
A configuration is set by linking the indicator
number, the four-pole input number and the out-
put code number by using an SPA protrol com-
mand.
The setting parameters S101…S116 which cor-
respond to the indicator code numbers
101…116 are reserved for the configuration
commands. Either the OPEN code (e.g. 20) or
the CLOSE code (e.g. 21) can be used as an
output code number. Also some other para-
meters, such as object type and the location of
open and closed status indicators, are specified
in the SPA instruction.
Fig. 6. Position, code number and colour of the
indicator units on the front panel of the control
module.
Setting
Configuration
= RED
= GREEN
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
COLUMN COLUMN COLUMN COLUMN
1
2
3
4