SPCJ 4D24
Combined overcurrent
and earth-fault relay
module
Contents
Features .......................................................................................................................... 2
Description of function .................................................................................................. 3
Block diagram ................................................................................................................. 5
Front panel ..................................................................................................................... 6
Operation indicators ....................................................................................................... 7
Settings ........................................................................................................................... 8
Programming switches .................................................................................................... 9
Measured data............................................................................................................... 13
Recorded information ................................................................................................... 14
Main menus and submenus of settings and registers ..................................................... 16
Time/current characteristics
(modified 2002-05) ...........................................................
18
Technical data ............................................................................................................... 26
Serial communication parameters ................................................................................. 27
Fault codes .................................................................................................................... 34
Features
A low-set overcurrent stage I> with a definite
time and six inverse time modes of operation
A high-set overcurrent stage I>> with a setting
range of 0.5...40 x I
n
. The operation of the high-
set overcurrent stage can be set out of function
A low-set neutral overcurrent stage I
0
> with a
setting range of 1.0...25.0 % I
n
and definite time
mode of operation
A high-set neutral overcurrent stage I
0
>> with
a setting range of 2.0...200 % I
n
. The opera-
tion of the high-set neutral over current stage
can be set out of function
Digital display of measured and set values and
sets of data recorded at the moment when faults
occur
All settings may be keyed in using the push-
buttons of the front panel or they may be set
using a personal computer
Continuous self-supervision including both
hardware and software. At a permanent fault
the alarm output relay operates and the other
outputs are blocked.