Ekip Dip protection release | 8 - Default parameters
8 - Default parameters
Ekip DIP default parameters
The Ekip Dip releases are supplied with the following default parameters, some adjustable with
the front DIPs (protections, Frequency, Neutral), other via front bus (Can, modules).
Protection/Parameter
Value
L
1 In; 144 s
S
(1)
Off; 0.1 s
I
4 In
G
(1)
Off; 0.1 s
Frequency
50 Hz
Neutral
Off (for 3P circuit-breaker).
50% (for 4P circuit-breaker)
Hardware trip
Disabled
Monitor Time
5 min
Local bus
Disabled
Alive LED
Disabled (Power LED on fixed)
(1)