![ABB SACE Emax 2 Installation, Operation And Maintenance Instructions Download Page 185](http://html.mh-extra.com/html/abb/sace-emax-2/sace-emax-2_installation-operation-and-maintenance-instructions_2172185.webp)
ABB | SACE Emax 2
Electronic accessories | 4 - Ekip Signalling 4K module
181 | © 2013
ABB |
1SDH001000R0002 - L7804
Continued from the previous page
The following table illustrates configuration parameters of the outputs:
Parameter Selectable values Default
Description
Signal
source
• None
• Prealarm L
• Delay L
• Delay S
• Opening L
• Opening S
• Opening G
• Opening I
• Every opening
• Every alarm
• Load LC1
(1)
• Load LC2
(1)
• CB Open
• CB Close
• Custom
(2)
None
The event that the output must activate, that is,
with which the contact must be:
• Closed, if set as NO.
• Open, if set as NC.
Delay
00…100.00 s
in steps of 0.01 s
0.00 s
Standby time after the selected event has taken
place, and before the output is activated (if the
event disappears before a time equal to the delay
has passed, the output is not activated). If 0.00 s
is selected, the value 300
μ
s is assigned to the
parameter.
Contact
Type
NO, NC
NO
• NO = Contact normally open.
• NC = Contact normally closed.
Self-
latching
Off, On
Off
• Off = The output is deactivated when the event
disappears.
• On = When the event disappears, the output is
kept active for the minimum time selected.
IMPORTANT: if the output is used for the
Power Controller function, self-latching
must not be enabled.
min
Activation
Time
0 ms, 100 ms,
200 ms, Power
Controller
0 ms
The "Power Controller" value must be selected
if the output is used for the Power Controller
function (see the chapter "21 - Ekip Power
Controller", on page 151). The output is then
kept active for a fixed time dictated by the
function, independently of the persistence of the
event that activated it.
On the contrary, with self-latching enabled, the
minimum time in which the output is kept active
(once the selected time has elapsed, the output
is kept active as long as the event that activated
it persists).
IMPORTANT: if the output is not used
for the Power Controller function, the
“Power Controller” value must not be
selected.
(1)
For the sources Load LC1 and Load LC2, see the chapter "9 - Touch protections", and the paragraph "
Current thresholds”, on page 91.
(2)
The Custom source is a combination of default events, that can be modified using the Ekip Connect
application so as to make the closing/opening of the contact correspond to a wide range of combinations
of the status bits of the release.
Continued on the next page