ABB | SACE Emax 2
Electronic accessories | 5 - Ekip Signalling 2K modules
189 | © 2013
ABB |
1SDH001000R0002 - L7804
Continued from the previous page
The following table illustrates configuration parameters of the inputs:
Parameter Selectable values Default
Description
Signal
source
Active open, Active
closed
Active closed
• Active open = To be considered
active, the input must be floating.
• Active closed = To be considered
active, the input must be connected to
its reference.
Delay
00…100.00 s
in steps of 0.01 s
0.01 s
Standby time after that the input has
changed state, before the change
of state is recognised (if the input is
reset before a time equal to the delay
has elapsed, the change of state is
nor recognised). If 0.00 s is selected,
the value 300
μ
s is assigned to the
parameter.
IMPORTANT: if the release is disconnected for at least 8 s, the outputs are
deactivated, except for those programmed to be activated in the case of
disconnection. Normal operation is restored on reconnection.
The following table illustrates the path from the display for accessing information on the
modules:
Information
Protection unit
Circuit-breaker
Modules
…
Ekip Signalling 2K-1
Ekip Signalling 2K-2
Ekip Signalling 2K-3
…
Power Controller
The information on the modules that can be displayed is as follows:
• The serial number and the software version.
• The logical state of the inputs (“Off” if not active, “On” if active).
• The state of the output contacts (“Open” if open, “Closed” if closed).
Continued on the next page