4.10.2
Binary output circuits
M11722-8 v3
Preferably, disconnect the binary output connector from the binary output cards. Check all
connected signals so that both load and polarity are in accordance with IED specifications.
4.11
Checking optical connections
M16022-2 v6
Check that the Tx and Rx optical connections are correct.
An IED equipped with optical connections requires a minimum depth of 180
mm for plastic fiber cables and 275 mm for glass fiber cables. Check the
allowed minimum bending radius from the optical cable manufacturer.
1MRK 505 293-UEN B
Section 4
Starting up
Breaker protection REQ650
33
Commissioning manual
© Copyright 2013 ABB. All rights reserved