IEC09000096-2-en.vsd
Tx
Tx
Rx
Rx
RJ-45
IED
PCM600
IEC09000096 V2 EN-US
Figure 2:
Point-to-point link between IED and PCM600 using a null-modem cable
The following description is an example valid for standard PCs using Microsoft Windows
operating system. The example is taken from a Laptop with one Ethernet interface.
Administrator rights are required to change the PC communication setup.
Some PCs have the feature to automatically detect that Tx signals from the IED
are received on the Tx pin on the PC. Thus, a straight (standard) Ethernet cable
can be used.
When a PC is connected to the IED and the setting
DHCPServer is set to On via the local HMI
path Main menu/Configuration/Communication/TCP-IP configuration/ETHFRNT:1/
DHCPServer, the IEDs DHCP server for the front port assigns an IP address for the PC. The PC
must be configured to obtain its IP address automatically as described in the following
procedure.
1.
Select Search programs and files in the Start menu in Windows.
Section 4
1MRK 505 293-UEN B
Starting up
26
Breaker protection REQ650
Commissioning manual
© Copyright 2013 ABB. All rights reserved