1MRS750915-MUM
REM 54_
75
Machine Terminal
Technical Reference Manual, General
5.1.13.8.
LON inputs and outputs via a LON bus
The machine terminal offers up to 32 freely programmable LON inputs and outputs
on the LON bus. The inputs and outputs use the LONMark Standard network
variable (NV type 83 = SNVT_state) for sending and receiving process data. The
LON inputs and outputs are accessible in the machine terminal configuration and
can be freely used for different types of data transfer between the machine terminals
and other devices that are able to communicate using the network variable of type
SNVT_state.
lonlog_b
Fig. 5.1.13.8.-1 Principle of connecting LON inputs and outputs to logic functions
of the machine terminal
The SNVT_state can be used to communicate the state of a set of 1 to 16 Boolean
values. Each bit indicates the state of the Boolean value with, for example, the
following interpretations:
The value field shows the current value of the digital inputs or outputs at the time of
reporting, or the latest value reported from the concerned device.
The SNVT_state can be used to transfer the state of 1 to 16 digital inputs, or to set
the state of 1 to 16 output bits or digital set-points.
0
1
off
on
inactive
active
disabled
enabled
low
high
false
true
normal
alarm
>1
nv16 nv16
nv16
I/O
REF 54_
>1
nv16 nv16
nv16
I/O
REF 54_
>1
nv16
RE_ 54_
SYS
LON
LON
RE_ 54_
>1
nv16 nv16
nv16
RE_ 54_
nv16 nv16
nv16
>1
nv16
nv16
Inter-
locking
Blocking
Open
enable
Close
enable
Close
Open
Reserve
Inter-
locking
Open
enable
Close
enable
Close
Open
Reserve
Inter-
locking
Blocking
Open
enable
Close
enable
Close
Open
Reserve
Select/Execute
Blocking
I/O
I/O
I/O
Summary of Contents for REM 54 Series
Page 1: ...Machine Terminal REM 54_ Technical Reference Manual General ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 22: ...22 ...
Page 26: ...26 ...
Page 92: ...92 ...
Page 94: ...94 ...
Page 102: ...102 ...
Page 104: ...104 ...
Page 108: ......
Page 109: ......