1MRS750915-MUM
REM 54_
29
Machine Terminal
Technical Reference Manual, General
5.1.1.2.
Measurement functions
The measurement function blocks are documented on the CD-ROM Technical
Descriptions of Functions.
5.1.1.3.
Control functions
The control functions are used to indicate the status of switching devices, i.e. circuit
breakers and disconnectors, and to execute open and close commands for
controllable switching devices of the switchgear. Furthermore, there are
supplementary functions for control logic purposes, e.g. on/off switches, MIMIC
alarm LED control, numerical data for MIMIC and logic controlled control position
selector.
The control functions configured with the Relay Configuration Tool can be
associated with object status indicators that are part of the MIMIC configuration
picture displayed on the HMI. The object status indicators are used to indicate the
status of switching devices via the MIMIC picture and to control them locally. For
more information about the MIMIC configuration, refer to section “MIMIC
configuration” on page 35.
Table 5.1.1.2-1 Measurement functions available for REM 54_
Function
Description
MEAI1
a
a. These functions are only supported in Release 2.0 or later, refer to section “Revision identification”
General measurement 1 / analog input on RTD1 card
MEAI2
a
General measurement 2 / analog input on RTD1 card
MEAI3
a
General measurement 3 / analog input on RTD1 card
MEAI4
a
General measurement 4 / analog input on RTD1 card
MEAI5
a
General measurement 5 / analog input on RTD1 card
MEAI6
a
General measurement 6 / analog input on RTD1 card
MEAI7
a
General measurement 7 / analog input on RTD1 card
MEAI8
a
General measurement 8 / analog input on RTD1 card
MEAO1
a
Analog output 1 on RTD1 card
MEAO2
a
Analog output 2 on RTD1 card
MEAO3
a
Analog output 3 on RTD1 card
MEAO4
a
Analog output 4 on RTD1 card
MECU1A
Neutral current measurement, stage A
MECU1B
Neutral current measurement, stage B
MECU3A
Three-phase current measurement, stage A
MEDREC16
Transient disturbance recorder
MEFR1
System frequency measurement
MEPE7
Three-phase power and energy measurement
MEVO1A
Residual voltage measurement, stage A
MEVO3A
Three-phase voltage measurement, stage A
Summary of Contents for REM 54 Series
Page 1: ...Machine Terminal REM 54_ Technical Reference Manual General ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 22: ...22 ...
Page 26: ...26 ...
Page 92: ...92 ...
Page 94: ...94 ...
Page 102: ...102 ...
Page 104: ...104 ...
Page 108: ......
Page 109: ......