1MRS750915-MUM
REM 54_
37
Machine Terminal
Technical Reference Manual, General
5.1.2.4.
Modbus configuration
To configure REM 54_ for Modbus, communication parameters need to be set.
These parameters can be found in the local menu of the machine terminal.
The Protocol Object Dictionary (POD) is a cross-reference table between
the machine terminal application and the Modbus protocol. The table defines what
information can be accessed from the device by using the protocol interface. The
POD contents can be downloaded to the machine terminal by using the Relay
Download Tool available in the CAP 505 tools. The new values of the
communication parameters take effect only after they have been stored and the
device has been reset. Modbus configurations for REM 543 including Modbus POD
cross-reference tables and their explanations are available on a separate CD-ROM,
REM 543 Modbus Configurations (see “Related documents” on page 10).
For more information about the configuration of the Modbus interface, refer to the
Modbus Remote Communication Protocol for REM 54_, Technical Description
manual (see “Related documents” on page 10).
5.1.2.5.
Rated frequency
The rated frequency of the machine terminal is set in association with configuration
via a dialog box in the Relay Configuration Tool. The set rated frequency cannot be
changed afterwards via the HMI or serial communication, but it can be read via the
global control parameter
Rated frequency
in the machine terminal.
5.1.3.
Parameters and events
The function blocks and I/O cards include a large number of parameters and events.
In addition, general parameters and events are provided, e.g. parameters for control
and communication as well as events for testing and self-supervision.
The function block specific parameters are listed in each function block description.
Moreover, all parameters and events for REM 54_ are listed in the parameter and
event lists. The function block descriptions as well as the parameter and event lists
are included on the CD-ROM Technical Descriptions of Functions (see “Related
documents” on page 10).
5.1.4.
Parameterization
To ensure that a protection function block protects the machine in the desired
manner, the default values of parameters are to be checked and properly set before
taking the function block into use.
The parameters can be set either locally over the HMI or externally via the serial
communication. Note that the Modbus parameters can only bet set locally.
5.1.4.1.
Local parameterization
When the parameters are set locally via the HMI, the setting parameters can be
chosen from the hierarchical menu structure. The desired language for parameter
description can also be selected. Detailed information about setting and navigation
is found in the RE_ 54_ Operator’s Manual.
Summary of Contents for REM 54 Series
Page 1: ...Machine Terminal REM 54_ Technical Reference Manual General ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 22: ...22 ...
Page 26: ...26 ...
Page 92: ...92 ...
Page 94: ...94 ...
Page 102: ...102 ...
Page 104: ...104 ...
Page 108: ......
Page 109: ......