1MRS750915-MUM
REM 54_
57
Machine Terminal
Technical Reference Manual, General
All range parameters can be set but only one is used. The value of the
Input mode
parameter determines which range parameter is used. The
Temperature range
parameter also defines the sensor type to be used, e.g. PT100.
Parameter
Values
Default
Voltage range
0 = 0...1V
0...1 V
1 = 0...5 V
2 = 1...5 V
3 = 0...10 V
4 = 2...10 V
5 = -5...5 V
6 = -10...10 V
Current range
0 = 0...1 mA
0...1 mA
1 = 0...5 mA
2 = 1...5 mA
3 = 0...10 mA
4 = 0...20 mA
5 = 4...20 mA
6 = -1...1 mA
7 = -2.5...2.5 mA
8 = -5...5 mA
9 = -10...10 mA
10 = -20...20 mA
Resistance range 0 = 0...100
Ω
0...100
Ω
1 = 0...200
Ω
2 = 0...500
Ω
3 = 0...1000
Ω
4 = 0...2000
Ω
5 = 0...5000
Ω
6 = 0...10000
Ω
Temperature
range
0 = Pt100 -45...150
°
C
Pt100 -45...150
°
C
1 = Pt100 -45...600
°
C
2 = Pt250 -45...150
°
C
3 = Pt250 -45...600
°
C
4 = Pt1000 -45...150
°
C
5 = Pt1000 -45...600
°
C
6 = Ni100 -45...150
°
C
7 = Ni100 -45...250
°
C
8 = Ni120 -45...150
°
C
9 = Ni120 -45...250
°
C
10 = Ni250 -45...150
°
C
11 = Ni250 -45...250
°
C
12 = Ni1000 -45...150
°
C
13 = Ni1000 -45...250
°
C
14 = Cu10 -45...150
°
C
15 = Ni120US -45...150
°
C
a
a. In Release 2.5 or later
16 = Ni120US -45...250
°
C
a
Summary of Contents for REM 54 Series