Machine Terminal
Technical Reference Manual, General
5.1.8.1.
High-speed double-pole power outputs (HSPO)
The high-speed power outputs PS1_4_HSPO1... PS1_4_HSPO5 can be connected
as double-pole outputs where the object to be controlled (e.g. a circuit breaker) is
electrically connected between the two relay contacts, see the figure below. The
high-speed double-pole power output is recommended to be used for tripping
purposes.
cbcoil_b
Fig. 5.1.8.1.-1 High-speed double-pole power outputs (HSPO)
Table 5.1.8-1
Digital outputs
REM 543
REM 545
Outputs
PS1_4_HSPO1
a
a. Trip Circuit Supervision function included
PS1_4_HSPO1
a
PS1_4_HSPO2
a
PS1_4_HSPO2
a
PS1_4_HSPO3 PS1_4_HSPO3
PS1_4_HSPO4
PS1_4_HSPO4
PS1_4_HSPO5
PS1_4_HSPO5
PS1_4_SO1 PS1_4_SO1
BIO1_5_SO1
BIO1_5_SO1
BIO1_5_SO2
BIO1_5_SO2
BIO1_5_SO3
BIO1_5_SO3
BIO1_5_SO4
BIO1_5_SO4
BIO1_5_SO5
BIO1_5_SO5
BIO1_5_SO6
BIO1_5_SO6
BIO2_7_PO1
BIO2_7_PO2
BIO2_7_PO3
BIO2_7_PO4
BIO2_7_PO5
BIO2_7_PO6
Outputs /
total
12
18
When TCS is used (see Table 5.1.8-1 on page 53), the outputs are
connected as shown in Figure 5.1.11.-1 on page 68.
+
-
CB
e.g.
PS1_4_HSPO1...
PS1_4_HSPO5