84
1MRS750915-MUM
Machine Terminal
Technical Reference Manual, General
REM 54_
Table 5.2.1-11 Data communication
Rear interface, connector X3.1
not used, reserved for future purposes
Rear interface, connector X3.2
RS-232 connection
the fibre-optic interface module RER 123 for SPA and a third-party
fully isolated RS-232/RS-485 converter for Modbus are needed for
galvanic isolation
protocol
SPA, Modbus
Phoenix RS-232/RS-485
converter
PSM-ME-RS232/RS485-P
converter’s cable
1MRS120535-C50 (50 cm)
1MRS120535-002 (2 m)
RER 123
1MRS090715
Rear interface, connector X3.3
RS-485 connection
the fibre-optic interface module RER 103 is needed for galvanic
isolation
protocol
SPA, LON
Rear interface, connector X3.4
RJ45 connection
galvanically isolated RJ45 connection for an external display panel
protocol
CAN
communication cable
1MRS 120511.001 (1 m)
1MRS 120511.003 (3 m)
Front panel
optical connection
protocol
SPA
communication cable
1MKC950001-2
SPA protocol
baud rates
4.8/9.6/19.2 kbps
start bits
1
data bits
7
parity
even
stop bits
1
LON protocol
bit rates
78.0 kbps/1.2 Mbps
Modbus protocol
baud rates
0,3/ 1,2/ 2,4/ 4,8 and 9,6 kbps
modbus modes
ASCII, RTU
Summary of Contents for REM 54 Series
Page 1: ...Machine Terminal REM 54_ Technical Reference Manual General ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 22: ...22 ...
Page 26: ...26 ...
Page 92: ...92 ...
Page 94: ...94 ...
Page 102: ...102 ...
Page 104: ...104 ...
Page 108: ......
Page 109: ......