Name
Values (Range)
Unit
Step
Default
Description
IHiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
IHiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
ILowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
ILowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
ILimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
FrDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
FrZeroDb
0 - 100000
m%
1
500
Zero point clamping
FrHiHiLim
0.000 - 100.000
Hz
0.001
65.000
High High limit (physical value)
FrHiLim
0.000 - 100.000
Hz
0.001
63.000
High limit (physical value)
FrLowLim
0.000 - 100.000
Hz
0.001
47.000
Low limit (physical value)
FrLowLowLim
0.000 - 100.000
Hz
0.001
45.000
Low Low limit (physical value)
FrLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
UAmpComp5
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate voltage at 5% of
Vn
UAmpComp30
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate voltage at 30% of
Vn
UAmpComp100
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate voltage at 100%
of Vn
IAmpComp5
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at 5% of In
IAmpComp30
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at 30% of
In
IAmpComp100
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at 100%
of In
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 5% of In
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 30% of In
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 100% of In
14.1.2.5
Monitored data
Table 349:
CVMMXN Monitored data
Name
Type
Values (Range)
Unit
Description
S
REAL
-
MVA
Apparent power magnitude of
deadband value
P
REAL
-
MW
Active power magnitude of
deadband value
Q
REAL
-
MVAr
Reactive power magnitude of
deadband value
Table continues on next page
1MRK 502 048-UUS A
Section 14
Monitoring
513
Technical manual